Ensure that the cylinder is situated on the scales before recovery is carried out.
g)
Start and use the recovery machine in accordance with manufacturer instructions.
h)
Do not overfill the cylinders to any more than 80% of volume liquid charge.
i)
Do not in any circumstances exceed the maximum working pressure of the cylinder.
j)
When the cylinders have been filled correctly and the process is completed, ensure
that the cylinders and equipment are removed from site promptly and all isolation
valves on the equipment are closed off.
k)
Recovered refrigerant must not be charged into another refrigeration system unless
cleaned and checked.
10. Labelling
Equipment should be labelled to state that it has been decommissioned and emptied of
refrigerant. The label must be dated and signed. Ensure that there are labels on the
equipment stating it contains flammable refrigerant.
11. Recovery
When removing refrigerant from a system for servicing or decommissioning, it is
recommended good practice that the refrigerants are completely removed in a safe
manner.
When transferring refrigerant into cylinders, ensure that only appropriate refrigerant
recovery cylinders are employed. Ensure that the correct number of cylinders is available
to hold total system charge. All cylinders marked for use should be designated and
labelled for the recovered refrigerant. Cylinders should be complete with pressure relief
valves and associated shutoff valves in good working order. Empty recovery cylinders
should be evacuated and cooled if possible before recovery occurs.