Herunterladen Inhalt Inhalt Diese Seite drucken

Endress+Hauser Tankvision Tank Scanner NXA820 Handbuch Seite 219

Beschreibung der gerätefunktionen; bestandsmanagement
Vorschau ausblenden Andere Handbücher für Tankvision Tank Scanner NXA820:
Inhaltsverzeichnis

Werbung

Tankvision
Endress+Hauser
Diagnose-Code
Kurztext
F329
All Gauges failed
F330
Connection lost
with Primary unit
F331
Connection lost
with Secondary
unit
F332
Module restarted
often
F333
One or more
Gauges failed
C485
Simulation Mode
On
C486
Manual Switch
Over ON
C487
Redundancy
activated
C488
Unit is active
C489
Unit is passive
F501
Database Fault
F502
Not Configured
C503
HART Tunneling
F504
Subscrip. Store
M505
Time Server
C506
Field Scan Off
C507
Interface Off
Ursache
All connected gauges are failed. Valid only
when redundancy is activated and
redundancy is configured as Switch by
Interface
Secondary redundant unit lost the
connection with Primary redundant unit
Primary redundant unit lost the connection
with Secondary redundant unit
Module is restarted more 5 times
One or more connected gauges have failed.
Valid only when redundancy is activated
and redundancy is configured as Switch by
Gauge
Field scan simulation mode is activated
Redundancy Manual Switch Over is
activated.
Redundancy feature is activated.
Redundant unit is active. i.e. field scan is
active.
Redundant unit is passive. i.e. field scan is in
standby mode
Database Failure
LAN Has Not Been Configured
Gauge Configuration In Progress
Subscription Store Cannot Be Found
The field scan has been stopped
The hostlink interface has been stopped
Menü "Systemadministration"
Mögliche Lösung
219

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis