w Pot_1 = measuring range 100...180W,
Pot_2 = measuring range 100...400W.
w Reaction with sensor break:
S_UP = action as input value higher than display range, 99999 blinking
S_do = action as input value lower than display range, 00000 blinking
w noCAL = no calibration. However, the scaling values can be changed
(x
/x
0
100
w CAL = Calibrate as follows:
With display 0!o, bring the transducer to span start and press
+
I and D to adjust the required start of display range, e.g. 0%.
Press M to confirm.
With display 100!o, bring the transducer to span end and press
+
I and D to adjust the required end of display range, e.g. 100%.
Press M to confirm.
One of 7 mathematic functions can be selected. With thermocouples, Pt100
and standard signals with linearization, the input variable of mathematic
function 1 is a temperature in °C or °F. With all other measuring ranges,
function 1 refers to the values for w
InPut
Measurement
&
Monitoring
control contact
Ct-
(
_)
9499-040-24701
fixed, w
/w
variable).
0
100
Func2
Func1
Function 2
Function 1
CHAr LAG1
TArA TrSt
,
,
SQrT QUAd Ln
IntE LEAd
,
,
,
LAG1
LG E-Fct
,
Ct-F2
or function key F
/w
adjusted in menu Input.
0
100
,
,
Ct-di
,
,
OutP
Analog
output
AlAr
Limit
contacts
Ct-Hi
Maximum
displ
value
Minimum
value
Ct-Lo
143. 2 1
9