ABB i-bus KNX Produkthandbuch Seite 48

Knx/enocean gateway
Vorschau ausblenden Andere Handbücher für i-bus KNX:
Inhaltsverzeichnis

Werbung

®

i-bus
KNX EG/A 32.2.1
Status_ Setpoint
Status_ Humidity
Humidity
Status_ Humidity
Status_ Humidity Setpoint
Status_Illumination
Illumination
Status_Illumination Setpoint
Status_ Illumination Over Range
Status_ On/Off Button
Control
Status_ Slide Switch
Status_ Occupancy Button
Occupancy
Status_ Occupancy Enablement
Status_ Contact State
Contact
Status_ Contact State
Status_ Fan Speed Manual/Auto
Fan Speed
Status_ Fan Speed
Status_ Fan Speed
Status_ Fan Speed Stage
Status_ Fan Speed Stage
Status_Supply Voltage
Voltage
Status_Supply Voltage Error Code
ABB STOTZ-KONTAKT GmbH
Eppelheimer Straße 82, 69123 Heidelberg, Germany
 +49 (0) 6221 701 607
 +49 (0) 6221 701 724
2 bytes
DPT_Value_Temp
2 bytes
DPT_Value_Humidity
1 byte
DPT_Scaling
2 bytes
DPT_Value_Humidity
2 bytes
DPT_Value_Lux
2 bytes
DPT_Value_Lux
1 bit
DPT_Bool
1 bit
DPT_Switch
1 bit
DPT_Switch
1 bit
DPT_Occupancy
1 bit
DPT_Enable
1 bit
DPT_OpenClose
1 bit
DPT_Window_Door
1 bit
DPT_Bool
1 byte
DPT_Scaling
1 byte
DPT_Enumerated
1 byte
DPT_Scaling
1 byte
DPT_Enumerated
2 bytes
DPT_Value_Volt
1 byte
DPT_Enumerated
9.001
R
T
ºC
9.007
R
T
%
5.001
R
T
%
9.007
R
T
%
9.004
R
T
lux
9.004
R
T
lux
1.002
R
T
0 – False; 1 – True
1.001
R
T
0 – Off; 1 - On
1.001
R
T
0 – Off/Night/PosI; 1 – On/Day/Pos0
1.018
R
T
0 – Not occupied; 1 – Occupied
1.003
R
T
0 – Disable; 1 – Enable
1.009
R
T
0 - Open; 1 - Closed
1.019
R
T
0 - Closed; 1 - Open
1.002
R
T
0 – Manual; 1 - Auto
5.001
R
T
%
5.010
R
T
0-Position 0; 1-Position 1; 2-Position 2; 3-Position 3
5.001
R
T
%
5.010
R
T
1 - Speed 1; 2 - Speed 2; 3 Speed 3; ...; 6 Speed 5
9.020
R
T
mV
5.010
R
T
Error Code
www.abb.com/knx