GAS PRESSURE SWITCH FOR VR46../VR86.. AND VK41../VK81..
APPLICATION
The gas pressure switch 45900438- functions as a minimum
inlet gas pressure supervision with a safe start interlock.
In combination with V(R)46../V(R)86.. or VK41../VK81..
gas controls a SPDT or SPST contact is operated as a
part of a safe start check circuit.
Burner will not be allowed to operate unless the gas
inlet pressure is above the set point.
DESCRIPTION
The gas pressure switch 45900438- is designed to be fitted
directly on the inlet pressure tap of a V(R)46../V(R)86.. or
VK41../VK81.. combination gas control by means of a
mounting/connection screw.
SPECIFICATIONS
Model (see table 1.)
45900438-1xx : gas pressure switch
45900438-2xx : gas pressure switch with cover
45900438-3xx : adjustable gas pressure switch with cover
45900438-4xx : adjustable gas pressure switch with cover
and terminal cap
Material
Diaphragm: NBR (Butadiene acrylon nitrile rubber
Housing: POM (Polyoximethylene)
Contacts: Gold plated or AgNi
Dimensions
See fig. 2., 3., 4. and 5.
Ambient temperature
-10 ... 70°C
COMBINATION GAS CONTROLS
Pressure setting (see table 1.)
Differential (depending on set-point):
up to 16 mbar: minimum 2.5 mbar.
16 ... 35 mbar: maximum 5.0 mbar.
Maximum sustained pressure
150 mbar.
Maximum operating pressure
100 mbar.
Terminals
Conform DIN 43650
Electrical connection
AMP faston 6.3 x 0.8 mm
Din plug conform DIN 43650
Enclosure
IP 00
Accessories
Description
Cable plug (conform DIN 43650)
Cover with screw
Contents
English .................................................................... Page 1
Deutsch .................................................................. Seite 3
1
45900438-
INSTRUCTION SHEET
Order number
45900429-050
45900429-051
MU1R-9165 1211RB-NE

Werbung

loading

Inhaltszusammenfassung für Honeywell 45900438-Serie

  • Seite 1 45900438- GAS PRESSURE SWITCH FOR VR46../VR86.. AND VK41../VK81.. COMBINATION GAS CONTROLS INSTRUCTION SHEET Pressure setting (see table 1.) Differential (depending on set-point): up to 16 mbar: minimum 2.5 mbar. 16 ... 35 mbar: maximum 5.0 mbar. Maximum sustained pressure 150 mbar. Maximum operating pressure 100 mbar.
  • Seite 2 Be sure the product is suitable for your application, frame of coil assembly. • otherwise consult Honeywell application Put the connection screw with ”O”-ring into the inlet pressure tap nipple. engineers. •...
  • Seite 3: Technische Daten

    WIRING Tightness test after installation WARNING • Paint pressure switch connection with a strong soap and water solution. Disconnect power supply before making • Start the appliance and check for bubbles. If a leak is wiring connections. found in the connection, remake the joint. Take care that wiring is in accordance with Adjustment (45900438-3xx only;...
  • Seite 4 Man vergewissere sich, ob der Druckwächter für Gasregelventile soll der Druckwächter mit dem die Anlage geeignet ist, ansonsten sollte man sich Verschlusshaken hinter dem Spulengehäuse befestigt von Honeywell ’s Anwendungsingenieuren beraten lassen. werden. • Montieren Sie die Anbauschraube mit Dichtungsringen Der Druckwächter darf nur von qualifiziertem...
  • Seite 5 Elektrische Anschlüße VORSICHT 12.6 Vor Beginn der Anschlußarbeiten ist die Netz-spannung auszuschalten. Die elektrischen Anschlüße müssen den 29.3 Bestimmungen des VDE und der zuständigen 31.5 Elektrizitätsversorgungs-Unternehmen entsprechen. Die Steckverbinder dürfen nicht mit Wasser in Berührung kommen. Gasdichtheitsprüfung nach der Installation Die Prüfung wird im Betriebszustand des Hauptbrenners durchgeführt.
  • Seite 6 16.5 Ø 12.6 29.3 31.5 90.5 12.5 28.5 35.8 Fig. 4. Dimensions (mm) gas pressure switch for VK41../VK81.. gas controls Abb. 4. Abmessungen (mm) Druckwächter geeignet für VK41../VK81.. Gasventile 16.5 Ø 12.6 37.5 Fig. 6. VR46../VR86.. with gas pressure switch 29.3 31.5 Abb.
  • Seite 7 STEP 53.8 STEP STEP STEP 60.3 59.5 66.5 66.5 92.5 75.5 75.5 92.5 36.7 36.7 Fig. 7. VK41../VK81.. with gas pressure switch Fig. 8. VK41../VK81.. with venturi system and gas pressure switch Abb. 7. VK41../VK81.. mit Druckwächter Abb. 8. VK41../VK81.. mit Venturi System und Druckwächter MU1R-9165 1211RB-NE...
  • Seite 8 Automation and Control Solutions Combustion Controls Europe Honeywell BV Phileas Foggstraat 7 7821 AJ Emmen The Netherlands Tel.: +31 (-)591 695911 Fax: +31 (-) 591 695200 http://europe.hbc.honeywell.com MU1R-9165 1211RB-NE...