Connection of Room Devices
Bus address
assignment
40
8.3

Wall Module SDW 10 / SDW 30

Configuration
Configuration of wall module SD 10 / SD 30 is done via parameter
03 of the heating- or mixing circuit on the controller. In addition, a
bus address must be selected at the wall module.
The assignment of a bus address occurs as follows:
Controller with bus address 10 (default) communicate with wall
modules having bus address 1 (for direct heating circuits, 2 (for
mixing circuit 1) or 3 (for mixing circuit 2).
SDW 10
bus address
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0
Central controller
No.
Bus address
1
10
1
10
1
10
2
20
2
20
2
20
3
30
3
30
3
30
4
40
4
40
4
40
5
50
5
50
5
50
undefined
Heating circuit
Unmixed heating circuit
Mixed heating circuit 1
Mixed heating circuit 2
Unmixed heating circuit
Mixed heating circuit 1
Mixed heating circuit 2
Unmixed heating circuit
Mixed heating circuit 1
Mixed heating circuit 2
Unmixed heating circuit
Mixed heating circuit 1
Mixed heating circuit 2
Unmixed heating circuit
Mixed heating circuit 1
Mixed heating circuit 2