8.2

Wall Module TF 22 / TFU 22

Configuration
Configuration and allocation is done via parameter 08, 09 or 10 in
the "Hydraulic" menu.
For any of the signals "Room temperature" and "Setpoint" one
variable input must be assigned.
The parameter setting in the "Hydraulic" menu for room sensor is
30 (for direct heating circuit), 31 (for mixing circuit 1) or 32 (for
mixing circuit 2).
The parameter setting in the "Hydraulic" menu for "Setpoint
deviation" and "Operating mode" is 50 (for direct heating circuit),
51 (for mixing circuit 1) and 52 (for mixing circuit 2).
Electrical connection occurs according to the assignment to
variable input 1 (VE1) ... variable input 3 (VE3) (Wall socket).
Example: Assignment of TF 22 to mixing circuits 1 (room sensor
to VE1 and setpoint / operating mode to VE2)
TF 22 / TFU 22
1
2
3

1 Actual value

3 GND
5 Setpoint and operating mode
4
5
Connection of Room Devices
SDC
X5
X6
1
Bus B
1
BUS A
2
GND
2
AF
3
GND
3
WF/KF
4
GND
4
SF
5
GND
5
VF1
6
GND
6
VE1
7
GND
7
VE2
8
GND
8
VE3
9
GND
9
VF2
10 GND
10 KVLF
11 GND
11 KSPF
12 GND
12 IMP