Herunterladen Inhalt Inhalt Diese Seite drucken

Installation Guidelines; Connection Diagrams; Terminal Allocation; Jumper Function - Honeywell IDENT-KEY 3 Montage, Anschluss, Anleitung

Vorschau ausblenden Andere Handbücher für IDENT-KEY 3:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Mounting and Connection Instructions IK3 Evaluation Unit Conventional
6.

Installation guidelines

All connection leads must be shielded cables stranded in pairs.
The corresponding line cross-sections can be found in the
detection central control unit (Chapter on lines). The shield terminal should also be kept as short as
possible to avoid the risk of an unintentional short circuit.
Debridge the wire jumper DB1 (Position see 7.1) if cable shield spikes also affect the operating
voltage.
For detailed information on installation, grounding and shielding, please refer to the Installation
Instructions of the corresponding intrusion detection central control unit as well as the brochure
"Electrical Installation of hazard detection systems"
7.

Connection diagrams

7.1

Terminal allocation

Tamper
LED
ready
LED
Monitoring resistors
Fault
Control function relay
(programmable)
a
Armed/disarmed
d
Fault
Hold-up indicator with storage
Blocking elements
BE 1/
AC door strike
BE 3
relay
(programmble)
7.2

Jumper function

PL2
1-2: CTS / 2-3: DSR (depending on type of printer used)
PL3
Both
closed:
Both
open:
PL4
Open:
Closed:
PL5
Open:
Closed:
Cover contact
PL5
SLIM-
Analogue
LOCK
inputs
+ 0V
1 0V 2 3
RS-485 with end of line resistor (see 7.5)
RS-485 without end of line resistor
Normal operation
Boot loader
PC/laptop
Serial printer
Installation Instructions
(P03061-15-000-XX).
Real-time clock with
lithium battery
Clear hold-up
alarm
PL4
Operating voltage U_BDT
for readers, 200 mA max.
current-limited, short circuit resistant
DB1
U_b
RS-485
of the intrusion
Buzzer
RS-232
PC/laptop
or
ser. printer
1
2
PL1
3
PL2
PL3
IK2 op. unit
or
IK2 block lock
*) programmble
37