Mounting and Connection Instructions IK3 Evaluation Unit Conventional
4.8
IK door release (AC function)
An
AC function
can be realized via a door strike at the lock bolt when the system is in a disarmed
state. A strike with load current or no-load current function can be used (see 4.3.1).
The type of authorization for door release is determined via the programming of the AC function: Only
PIN, only key, PIN and key.
Authorization is followed by a
A permanent release that is controlled via time zones or that can be switched on/off via a control func-
tion, can also be defined via the programming.
The door can also be released via a button. This is a normal door strike function.
If the door break-in identification is activated, the door may only be released from the inside via the
input AC release button.
If "Open time not programmed" is defined in the programming, there is no AC function.
However, another function can be allocated to the door strike relay via the programming. In
this case, actuation is also possible in an armed state.
4.9

Forced unlocking

Irrespective of the arming/disarming state, the door can be opened by a button at all times. In the
armed state, the door strike is not only released, but the blocking elements also move into the posi-
tion "OPEN". The armed state of the system remains active.
This function is possible, e.g. with an "Emergency open" button.
The "Forced unlocking" state remains active as long as the input is actuated.
The door strike relay is not actuated, if "Open time not programmed" is defined in the
programming.
If the EU is used as a BPS system, this input is allocated (fixed) for controlling the 2nd
door strike at the inside door. This function is only possible if the BPS function "Delay
time" and "Release time" have been programmed at greater than "0:00". If both times are
set at "0:00", the original function remains as "forced unlocking".
4.10

Hold-up alarm

A triggered hold-up alarm remains stored until it is cleared. The output "Hold-up indicator" is intended
for the transmitted indication (e.g. with a LED). A programmable output can be used for transmitting a
hold-up alarm.
Clear hold-up alarm: Via a control function (see 4.7) or via the button in the EU (press button approx.
10 seconds
).
Note:
With a BPS system, the output "Hold-up indicator" is actuated for 1 second, internally the
alarm remains stored until it is reset.
time-controlled door release
according to the programming.