Mounting and Connection Instructions IK3 Evaluation Unit Conventional
4.
Description of connection and functions
4.1

Connection to central control unit

As far as the central control unit is concerned, the EU functions like a block lock. In addition to the
block lock connections, outputs for tamper, fault and hold-up (via programmable output) are avail-
able.
4.2

Reader connections

4.2.1

RS-485 interface, possible readers

Up to 4 readers (types mixed as required) can be operated on the RS-485 bus. Possible readers:
User
IK3 Reader proX
Accentic Reader mifare
luminAXS Reader proX
Reader for Siedle Vario proX
Insertic proX
Insertic-50 proX
ZK Reader proX1 "Classic"
"Insertic-50" proX1 from V. 69769c.
4.2.2

IK2 switching devices

Operation of a random IK2 operating unit or an IK2 block lock. A special output U_BDT is available for
supplying the voltage of the reader that is short-circuit resistant and current-limited (max. 200 mA).
The signals "Buzzer/ Disarmed / Alarm / Data / Release" are connected to a separate terminal.
4.3

Electromechanical locking

4.3.1
AC door strike
!
Strike with load current function:
the power supply fail, the door is locked.
!
Strike with no-load current function:
the power supply fail, the door is unlocked.
If the used door strike is equipped with a monitoring contact, this can be used for the door monitoring
time. The monitoring contact reacts automatically to the door position "Open" or "Closed". When the
door is closed, the contact is also closed.
Firmware
from V01.xx 023320
from V02.xx 026423
from V04.xx 027911
from V02.xx 023340 ff
from V03.xx 027669.10
from V03.xx ---
from V02.xx 026481
(Strike with load current / no-load current function)
The catch bolt is unlocked when power is applied. Should
The catch bolt is locked when power is applied. Should
EU
with keypad
Item no.
without keypad
023322.99
026422
027910
023330 ff
027668.10
027661.10
026480.10