Honeywell 45.900.438 Serie Handbuch Seite 2

Gasdruckwächter für vr46../vr86 und vk41../vk81.. regelventile

Werbung

Code
Applicable for
V(R)46..
VK41..
V(R)86..
VK81..
101
Yes
No
102
Yes
No
103
Yes
No
104
Yes
No
105
Yes
No
106
Yes
No
107
No
Yes
108
No
Yes
109
No
Yes
110
No
Yes
111*
No
Yes
203**
Yes
No
209**
No
Yes
301
Yes
No
* Only for VK41../VK81.. with venturi system
** With mounted cover
Material of contacts
AgNi
Gold plated
*
values between brackets (..) valid for cos ♥ = 0.6
INSTALLATION, ADJUSTMENT AND
CHECKOUT
IMPORTANT
Be sure the product is suitable for your application,
otherwise consult Honeywell application engineers.
Installer must be a trained experienced service man
Turn off gas supply before starting installation.
Disconnect power supply to prevent electrical shock
and/or equipment damage.
Do not turn sealed adjustment screw, the switch point
is factory set.
Adjustments should be made by qualified persons
only.
Mounting limitations
VK41../VK81.. gas controls provided with gas pressure
1
switch gives limitations in mounting position of
valve/venturi system.
VK41../VK81.. gas controls with venturi system should
2
be provided with gas pressure switch according fig. 5.
MU1R- -9165 0005R5- -NE
Table 1. Models gas pressure switch 45.900.438- -
Switch point (mbar)
ON
15.5  1
12.5  1
15.5  1
12.5  1
35  3
35  3
15.5  1
35  3
15.5  1
12.5  1
12.5  1
15.5  1
15.5  1
--
Table 2. Electrical rating, contact resistance
Electrical rating
(resistive duty)*
250 Vac, 5 (0.5) A
24 Vac/dc, 100 (50) mA
Switch
type
type
OFF
131
SPST
10  1
SPST
13  1
SPST
10  1
SPST
30  3
SPST
30  3
SPST
13  1
SPST
30  3
SPST
13  1
SPST
10  1
SPST
10  1
SPST
13  1
SPST
13  1
SPST
8  1
SPDT
Minimum electrical
rating
24 Vac, 50 mA
5 Vac/dc, 10 mA
Mounting (See fig. 6., 7. and 8.)
 Remove pressure tap screw from the inlet pressure tap
nipple of the gas control. (if applicable).
 Position the gas pressure switch over the inlet pressure tap
nipple of the gas control.
For VK41../VK81.. gas controls hook--up the gas pressure
switch behind metal frame of coil assembly.
 Put the connection screw with "O"--ring into the inlet
pressure tap nipple.
 Tighten with a 9 mm box--spanner the connection screw
with a torque of 3 Nm.
When inlet pressure tap screw (on top of connection
screw) has been used, retighten the screw
finger tight.
CAUTION
Do not turn connection screw more tight then specified
above because of possible damage.
2
Contact ma-
Color of sea-
terial
terial
ling on set-
ling on set
ting screw
gold plated
red
gold plated
yellow
AgNi
blue
AgNi
green
gold plated
brown
AgNi
black
gold plated
red
gold plated
brown
AgNi
blue
AgNi
green
gold plated
yellow
AgNi
blue
AgNi
blue
AgNi
--
Switch type
Contact resistance
(initial)
SPDT or SPST
< 80 mτ
SPDT or SPST
< 80 mτ
Adjustable
pressure
pressure
range (mbar)
--
--
--
--
--
--
--
--
--
--
--
--
--
2 ... 17
1
/
turn beyond
4