GAS PRESSURE SWITCH FOR VR46../VR86.. AND VK41../VK81..
APPLICATION
The gas pressure switch 45.900.438-- functions as a minimum
inlet gas pressure supervision with a safe start interlock.
In combination with V(R)46../V(R)86.. or VK41../VK81.. gas
controls a SPDT or SPST contact is operated as a part of a
safe start check circuit.
Burner will not be allowed to operate unless the gas inlet
pressure is above the set point.
DESCRIPTION
The gas pressure switch 45.900.438-- is designed to be fitted
directly on the inlet pressure tap of a V(R)46../V(R)86.. or
VK41../VK81.. combination gas control by means of a
mounting/connection screw.
SPECIFICATIONS
Model (See table 1.)
45.900.438--1xx : gas pressure switch
45.900.438--2xx : gas pressure switch with cover
45.900.438--3xx : adjustable gas pressure switch with cover
Material
Diaphragm: NBR (Butadiene acrylon nitrile rubber
Housing: POM (Polyoximethylene)
Contacts: Gold plated or AgNi
Dimensions
See fig. 2., 3., 4. and 5.
Ambient temperature
--10 ... 70 _C
COMBINATION GAS CONTROLS
Pressure setting (see table 1.)
Differential (depending on set--point):
up to 16 mbar: minimum 2.5 mbar.
16 ... 35 mbar: maximum 5.0 mbar.
Maximum sustained pressure
150 mbar.
Maximum operating pressure
100 mbar.
Terminals
Conform DIN 43650
Electrical connection
AMP faston 6.3 x 0.8 mm
Din plug conform DIN 43650
Enclosure
IP 00
Accessories
Description
Cable plug (conform DIN 43650)
Cover with screw
English
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Deutsch
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
45.900.438-
INSTRUCTION SHEET
Order number
45.900.429--050
45.900.429--051
Contents
MU1R- -9165 0005R5- -NE
Page 1
Seite 3

Werbung

loading

Inhaltszusammenfassung für Honeywell 45.900.438 Serie

  • Seite 1 45.900.438- GAS PRESSURE SWITCH FOR VR46../VR86.. AND VK41../VK81.. COMBINATION GAS CONTROLS INSTRUCTION SHEET Pressure setting (see table 1.) Differential (depending on set--point): up to 16 mbar: minimum 2.5 mbar. 16 ... 35 mbar: maximum 5.0 mbar. Maximum sustained pressure 150 mbar. Maximum operating pressure 100 mbar.
  • Seite 2 For VK41../VK81.. gas controls hook--up the gas pressure Be sure the product is suitable for your application, switch behind metal frame of coil assembly. otherwise consult Honeywell application engineers.  Put the connection screw with ”O”--ring into the inlet pressure tap nipple.
  • Seite 3: Verwendung

    WIRING Tightness test after installation  Paint pressure switch connection with a strong soap and water solution. WARNING  Start the appliance and check for bubbles. If a leak is found in the connection, remake the joint. Disconnect power supply before making wiring Adjustment (45.900.438- 3xx only;...
  • Seite 4: Einbau Und Prüfung

    Man vergewissere sich, ob der Druckwächter für die  Schieben Sie den Druckwächter über den Druckmeß-- Anlage geeignet ist, ansonsten sollte man sich von nippel. Honeywell ’s Anwendungsingenieuren beraten Bei Anwendung der VK41../VK81.. Gasregelventile soll der lassen. Druckwächter mit dem Verschlusshaken hinter dem Der Druckwächter darf nur von qualifiziertem...
  • Seite 5 Elektrische Anschlüße VORSICHT Ø12.6 Vor Beginn der Anschlußarbeiten ist die Netz-- spannung auszuschalten. 29.3 Die elektrischen Anschlüße müssen den Bestimmungen des VDE und der zuständigen 31.5 Elektrizitätsversorgungs--Unternehmen entsprechen. Die Steckverbinder dürfen nicht mit Wasser in Berührung kommen. Gasdichtheitsprüfung nach der Installation Die Prüfung wird im Betriebszustand des Hauptbrenners durchgeführt.
  • Seite 6 16.5 Ø 12.6 29.3 90.5 31.5 12.5 28.5 35.8 Fig. 4. Dimensions (mm) gas pressure switch for VK41../VK81.. gas controls Abb. 4. Abmessungen (mm) Druckwächter geeignet für VK41../VK81.. Gasventile 16.5 37.5 Ø 12.6 Fig. 6. VR46../VR86.. with gas pressure switch 29.3 Abb.
  • Seite 7 STEP 53.8 STEP 60.3 59.5 66.5 66.5 92.5 75.5 75.5 92.5 36.7 36.7 Fig. 8. VK41../VK81.. with venturi system and gas Fig. 7. VK41../VK81.. with gas pressure switch pressure switch Abb. 7. VK41../VK81.. mit Druckwächter Abb. 8. VK41../VK81.. mit Venturi System und Druckwächter MU1R- -9165 0005R5- -NE...
  • Seite 8 Combustion Controls Center Europe Honeywell BV Phileas Foggstraat 7, Emmen P.O. Box 83 7800 AB Emmen NL- - The Netherlands Tel: +31 (0)591 695911 Fax: +31 (0)591 695200 MU1R- -9165 0005R5- -NE...