Herunterladen Inhalt Inhalt Diese Seite drucken

Parameterization / Basic Settings; Compensation - Pepperl+Fuchs LUC4T-G5S-IU-V15 Handbuch

Serie luc4
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

V15 / V1* connection
Pin
cable color
1
2
3
4
5*
* not connected with the V1-plug
4.

Parameterization / basic settings

The parameterization is done according to the short reference in section 7.
4.1 Calibration
You have two possibilities to calibrate the measuring range of the sensor: First you can do the calibration with
demounted sensor or in mounted position with the medium.
You do the calibration with two levels: „empty" and „full". In mounted position you fill the vessel according to the
position you want to calibrate and teach in this position. In position „empty" you set the output to 4 mA (0 V) and to
20 mA (10 V) in position „full".
If you want to calibrate the demounted sensor you have to simulate the level. Connect the sensor to power and direct
the sensor to a wall such that the distance between the sensor and the wall equals the „empty" level. After teaching
in this distance you do the same for the „full" level. The sketch shows this procedure. The advantage of this method
is that you do have a full working system when you run your installation first time.
Full
level
Subject to reasonable modifications due to technical advances.
16
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-22 22 · USA (3 30) 4 25 35 55 · Singapore 779 90 91 · Internet http://www.pepperl-fuchs.com
brown
white
blue
black
grey
abbreviation
BN
WH
BU
BK
GR
Empty level
Parameterization / Pre set
connection
U+
Uout
GND
Iout
n.c.
Copyright Pepperl+Fuchs, Printed in Germany

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis