Mounting and Connection Instructions Block Lock Module BUS-2/BUS-1
3.2

Detector group inputs

3.2.1

Properties

The four differential detector groups operate with a stabilized voltage of 8 V DC, the internal
resistance is 1k.
The terminals are suitable for Z wiring.
3.2.2

Monitoring range

- Detector group DG1, DG3 and Dg4:
Monitoring range 12k1 ±20%.
The detector group inputs MG1, MG3 and MG4 are designed as multi-balanced inputs.
If required, you can assign an individual resistance template. Further information can be
found in the programming manual IQ PanelControl for MB-Secure panel.
- Detector group DG2 „Disarmed/armed"
This detector group evaluates the state of the switching device: "disarmed/armed".
Therefor the detector group provides 2 or 3 monitoring ranges, (depending on the operating
mode of the switching device). The operating mode is set via DIP switch (see 4.3).
Operating mode "Lock function"
1.
12k1 ±20%. Switch in position "disarmed".
2.
6k05 ±20%. Switch in position "armed".
Operating mode "Mid-position" (Switch with neutral mid-position)
1.
18k15, from -8% to +20%. Switch in neutral mid-position.
2.
12k1 ±20%. Contact in position "disarmed".
3.
6k05 ±20%. Contact in position "armed".
Values outside the monitoring ranges are evaluated as tamper.
3.2.3
Functions of the detector groups (DG1, DG3 and DG4)
Detector group DG1 "Tamper"
(Only with the panel 561-MB100 this detector group is assigned to tamper function). This
differential input is used to monitor the tamper criteria of the switching device (e.g. protection
against drilling of the block lock).
Detector group DG3 "Bolt switching contact"
The bolt switching contact monitores the state of the lock bolt: locked/unlocked.
The detector group has effect on the positive drive.
Detector group DG4 "Opening contact"
The opening contact (e.g. magnetic contact ) monitores the state of the door: closed/open.
Additional the detector group DG4 provides the "clear function", suitable for passive glass
breakage sensors.
The combination of opening contact with passive glass breakage sensor is possible (see
"Connection diagrams" chapter 6.6).
(e.g. Block Lock)