Herunterladen Diese Seite drucken

Endress+Hauser Nivotester FTL325P Bedienungsanleitung Seite 36

Vorschau ausblenden Andere Handbücher für Nivotester FTL325P:

Werbung

en -Trouble-shooting
36
Fault
Reason
Does not
No power
switch
(green LED does not light up)
Electronic defect
Contacts welded together
(after short-circuit)
Measuring transmitter
defective
Switches
Incorrect setting of change-
incorrectly
over switch for limit signal in
FTL325P
Permanent
Interrupt or short-circuit line
alarm signal
to measuring transmitter
Measuring transmitter
electronics defective
Nivotester defective
Switches
FEL57, Behaviour during
incorrectly
switch-ontest (functional
afterpower
test)
failure
Remedy
Check power
Replace FTL325P
Replace FTL325P;
connect a fuse into contactor
circuit
Replace measuring transmitter
Correctly set change-over
switch behind front panel,
p. 15 ff
Check line
Replace measuring transmitter
electronics
Replace FTL325P
Observe switching behaviour of
FEL57; after a power failure
block the system control for up
to about 45 s
Endress+Hauser

Werbung

loading