Electro-mechanical fan-coil thermostat
with heating/cooling switch
and fan speed selector
RRT025A is an electro-mechanical room thermostat for wall moun-
ting. It has an On/Off switch, a heating/cooling switch and a fan
speed selector switch.
It is intended for use with a thermal actuator, a spring-return actua-
tor or a solenoid valve.
Technical data
Fan switch
10 (3) A 250 V AC. Total load, actuator +
Thermostat
1 A 250 V AC
Setpoint range
10...30°C
Switching differential
0.6K
Protection degree
IP30
Installing
Loosen the cover retaining screw at the top of the unit. Remove the
cover by pulling outwards at the top.
Mount the RRT025A in a suitable location with good air circulation.
The mounting holes have c:c 60 mm distance to fit onto a wallbox.
Wiring
Wire the unit in accordance with the wiring diagram.
N.B. RRT025A can be used for either heating or cooling depending
on the setting of the heating/cooling selector, but not both at the
same time.
Terminal 1
250 V AC in, heating/cooling and fan control
Terminal 2
Fan, intermediate speed
Terminal 3
Fan, low speed
Terminal 4
Neutral
Terminal 5
Heating/Cooling output
Terminal 6
Fan, high speed
NOTE: The fan must be of a type with three separate windings for
High, medium and Low speed.
HEAT/OFF/COOL
In the HEAT position the output on terminal 5 will be activated
when the temperature falls below the setpoint value.
In the COOL position the output on terminal 5 will be activated
when the temperature rises above the setpoint value.
In the OFF position the power is cut both to the thermostat func-
tion and the fan control.
fan
HIGH/MED/LOW Fan speed selector
When in position HIGH the output on terminal 6 will be active.
When in position MED the output on terminal 2 will be active.
When in position LOW the output on terminal 3 will be active.
NOTE: The fan must be of a type with three separate windings
for High, medium and Low speed.
This product conforms with the requirements of European LVD
standards EN 60730-2-9:2002 and carries the CE mark.