Direkt gekoppelte aktuatoren mit federrückstellung
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

3 NM SERIES SPRING RETURN DIRECT COUPLED ACTUATORS
timing. When the signal is disconnected, the actuator will
drive to the fully closed position with normal operation
timing.
CAUTION
Do not use fast test mode for permanent
operation.
Lifetime will be reduced if this mode is used
permanently. This mode is intended to be used only
for initial commissioning/testing of the system
after installation. Power consumption is not
specified in this mode.
Auxiliary Switches
Some models include Auxiliary switches. For wiring details
see Fig. 10.
Actuator Override
To override the control signal (for freeze protection or
similar applications):
1. Override to full open (fast commissioning, drive
mode lower than 30 sec):
a. Disconnect the input signal (from terminal 3).
b. Apply 24 VAC to terminal 3.
c. See Fig. 16.
2. Return to full closed:
a. Disconnect the input signal (from terminal 3).
b. See Fig. 17.
CLASS 2
1
24 VAC
2
0/2 TO 10 VDC
PROPORTIONING
CONTROLLER
+
SPDT
FEEDBACK
1
LINE VOLTAGE POWER SUPPLY.
PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
2
24 VDC SUPPLY ACCEPTABLE.
3
SET SWITCH TO MODULATING IF AVAILABLE.
Fig. 16. Override to open position.
31-00141M—02
ACTUATOR
1
RED
V
2
BLACK
3
0°-90°/MODULATING
WHITE
4
BROWN
90°-0°/FEEDBACK
2-10 VDC
10-2 VDC
0-10 VDC
3
10-0 VDC
FLOATING, FWD
FLOATING, REV
M37323
8
CLASS 2
1
24 VAC
2
0/2 TO 10 VDC
PROPORTIONING
CONTROLLER
+
SPST
FEEDBACK
1
LINE VOLTAGE POWER SUPPLY.
PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
2
24 VDC SUPPLY ACCEPTABLE.
3
SET SWITCH TO MODULATING.
Fig. 17. Return to closed position.
CHECKOUT
Modulating/Floating Operation
1. Mount actuator for required application (either
clockwise
or counterclockwise
open the damper).
2. Connect power to power and common wire. (See Fig.
10 and Table 3.)
3. Set "Mode Select" dial to desired control signal.
(See Fig. 5.)
4. Apply control signal for actuator full open or full
closed position. (See Fig. 10 and Table 3.)
a. (0)2-10 VDC: apply 10 VDC signal to control wire
(WHITE).
b. 10-(0)2 VDC: apply (0)2 VDC signal to control
wire (WHITE).
c. (0)4-20 mA: apply 20 mA signal to control wire
(WHITE).
d. 20-(0)4mA: apply (0)4 mA signal to control wire
(WHITE).
e. Floating: apply 24 VAC to appropriate 0°-90°
(WHITE) or 90°-0° (BROWN) wire.
5. Actuator drives to full open or full closed position.
6. Apply control signal for actuator 0% position.
(See Fig. 10 and Table 3.)
a. (0)2-10 VDC: apply (0)2 VDC signal to control
wire (WHITE).
b. 10-(0)2 VDC: apply 10 VDC signal to control wire
(WHITE).
c. (0)4-20 mA: apply (0)4 mA signal to control wire
(WHITE).
d. 20-(0)4mA: apply 20 mA signal to control wire
(WHITE).
e. Floating: apply 24 VAC to appropriate 0°-90°
(WHITE) or 90°-0° (BROWN) wire.
7. Actuator drives to full open or full closed position.
ACTUATOR
1
RED
V
2
BLACK
0°-90°/MODULATING
3
WHITE
4
BROWN
90°-0°/FEEDBACK
2-10 VDC
10-2 VDC
0-10 VDC
3
10-0 VDC
FLOATING, FWD
FLOATING, REV
M37324
rotation to