5.2 QUICK SETUP PARAMETERS

Code
P1.1
P1.2
P1.3
P1.4
P1.5
P1.7
P1.15 Torque boost
P2.1
P2.2
P2.3
P3.1
P3.2
P3.3
P3.4
P3.5
P3.6
P3.7
Table 2: Quick setup parameters (Complete parameter list and parameter descriptions
can be found from Complete SmartDrive Compact User Manual available on product
CD or at: http://ecc.emea.honeywell.com/inverter)
Monitoring & Parameters
Parameter
Min
Motor nominal
180
voltage
Motor nom. fre-
30
quency
Motor nominal
300
speed
Motor nominal
0,2 x
current
I
Nunit
ϕ
0,30
Motor cos
Current limit
0,2 x
I
Nunit
0
Control place
1
Start function
0
Stop function
0
Min frequency
0,00
Max frequency
P3.1
I/O reference
0
Preset speed 0
0,00
Preset speed 1
0,00
Preset speed 2
0,00
Preset speed 3
0,00
Max
Unit Default
500
V
230
400
320
Hz
50,00
2000
rpm
1440
0
1,5 x
A
I
Nunit
I
Nunit
1,00
0,85
2 x
A
1,5 x
I
I
Nunit
Nunit
1
0
3
1
1
0
1
0
P3.2
Hz
0,00
320
Hz
50,00
4
3
P3.2
Hz
5,00
P3.2
Hz
10,00
P3.2
Hz
15,00
P3.2
Hz
20,00
ID
Note
110 Check rating plate on the
motor
111 Check rating plate on the
motor
112 Default applies for a
4-pole motor.
113 Check rating plate on the
motor
120 Check rating plate on the
motor
107
109 0 = Not used 1 = Used
125 1 = I/O termina
2 = Keypad
3 = Fieldbus
505 0 = Ramp 1 = Flying start
506 0 = Coasting 1 = Ramp
101
102
117 0 = Preset Speeds (0-7)
1 = Keypad Reference
2 = Fieldbus Reference
3 = AI1
4 = AI2
124 Activated by digital inputs
105 Activated by digital inputs
106 Activated by digital inputs
126 Activated by digital inputs