Mounting and Connection Instructions -
4.

Programming

BUS-2 address
The DIP switches (address switch S1) in the separating
module are for setting the BUS-2 user address. The
individual codes can be found in the programming
protocol of the intrusion detection central control unit.
Possible address range: 0 to 63
Ensure that addresses are not allocated twice in the bus.
The term "
separating module
bus in the programming of the central control units.
(
)
Type No.: 06
5.

Installation guidelines

The BUS connection lead
to the diagram below.
The corresponding line cross-sections can be found in the
detection central control unit (Chapter on lines). The shield terminal should also be kept as short as
possible to avoid the risk of an unintentional short circuit.
Note:
BUS-2 connection technology does not require a terminating resistor.
loop
module
+12 V DC
U_b
0 V
Data
0 V
Separating
" is used as a type of
must
be a shielded cable, stranded in pairs and the cores laid according
BUS-2
Module
BUS-2
Addresss switch S1
ON
Switch position in example:
Address 5
Installation Manual
BUS-2
separating module BUS-2
32
16
8
4
2
1
Address value
OFF
Switch position
set!
of the intrusion
+12 V DC
0 V
Data
0 V