SDC / DHC 43
11 Technical Data
11.1 Controller
Power supply
Frequency
Consumption
Required fuse
Contact load of relais
Businterface
Powersupply via Bus
Ambiant temperarture
Storage temperature
Protection
Protection class acc. EN 60730
Protection class acc. EN 60529
Radio interference suppresion
Immunity
EG-conformity
Dimensions
Housing material
Connection technique
11.2 Sensor Resistance Values
Sensor Resistance Values Honeywell / Centra NTC 20 kΏ Sensor for AF,
WF/KF, SF, VF1, VF2, VE1 (Setting not for AGF), VE2, VE3, KSPF
°C
KΏ
°C
-20
220,6
0
-18
195,4
2
-16
173,5
4
-14
154,2
6
MU1H-0207 GE51R0902
230V +6%/ -10%
50...60Hz
max. 5,8VA
max. 6,3A slow
2 (2) A
In order to connect external units (wall
modules, PC, modem or gateway)
12V/ 150mA
0....+50°C
-25....+60°C
IP 30
II
III
EN 55014 (1993)
EN 55104 (1995)
89/336/EWG
144 x 96 x 75 mm (B x H x T): DIN size
ABS with Antistatic
Pluggable screw terminals
kΏ
°C
kΏ
70,20
20
25,34
63,04
25
20,00
56,69
30
15,88
51,05
35
12,69
46
°C
kΏ
70
3,100
75
2,587
80
2,168
85
1,824