FOR SERVICE PERSONNEL ONLY
• Carefully read through the procedures of proper installation
before starting installation work.
• The sales agent should inform customers regarding the correct
operation of installation.
HITACHI SPLIT UNIT AIR CONDITIONER
INSTALLATION MANUAL
Tools Needed For Installation Work
is exclusive use tool for R410A) • ª · Screwdriver
(Mark
OUTDOOR UNIT
• Measuring Tape • Knife • Saw • ø65mm Power Drill
• Hexagonal Wrench Key (
4mm) • Wrench (14,17,19,
RAC-25NX2
22mm)
Gas leakage Detector • Pipe Cutter • Putty
RAC-35NX2
• Vinyl Tape • Pliers • Flare Tool
RAC-50NX2
Manifold Valve
Charge Hose
Vacuum Pump
SAFETY PRECAUTION
• Read the safety precautions carefully before operating the unit.
• The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
WARNING ............. Incorrect methods of installation may cause death or serious injury.
CAUTION .............. Improper installation may result in serious consequence.
Make sure to connect earth line.
This sign in the À gures indicates prohibition.
Be sure that the unit operates in proper condition after installation. Explain to customer the proper operation and maintenance of the unit
as described in the user's guide. Ask customers to keep this installation manual together with the instruction manual.
WARNING
• Please request your sales agent or qualiÀ ed technician to install your unit. Water leakage, short circuit or À re may occur if you do the installation work
yourself.
• Please observe the installation stated in the installation manual during the process of installation. Improper installation may cause water leakage, electric
shock and À re.
• Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the units may collapse and
impose danger.
• Observe the rules and regulations of the electrical installation and the methods described in the installation manual when dealing with the electrical
work. Use cables which are approved ofÀ cial in your country. Be sure to use the speciÀ ed circuit. A short circuit and À re may occur due to the use of low
quality wire or improper work.
• Be sure to use the speciÀ ed cables for connecting the indoor and outdoor units. Please ensure that the connections are tight after the conductors of the
wire are inserted into the terminals to prevent the external force is being applied to the connection section of the terminal base. Improper insertion and
loose contact may cause over-heating and À re.
• Please use the speciÀ ed components for installation work. Otherwise, the unit may collapse or water leakage, electric shock, À re or stronger vibration
may occur.
• Be sure to use the speciÀ ed piping set for R410A. Otherwise, this may result in broken copper pipes or faults.
• When installing or transferring an air conditioner to another location, make sure that air other than the speciÀ ed refrigerant (R410A) does not enter the
refrigeration cycle. If other air should enter, the pressure level of the refrigeration cycle may increase abnormally which could result in a rupture and injury.
• Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with À re, a poisonous gas may occur.
• After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into the room, coming into
contact with À re in the fan-driven heater, space heater, etc., a poisonous gas may occur.
• Unauthorized modiÀ cations to the air conditioner may be dangerous. If a breakdown occurs please call a qualiÀ ed air conditioner technician or electrician.
Improper repairs may result in water leakage, electric shock and À re, etc.
• Be sure to connect the earth line from the power supply wire to the outdoor unit and between the outdoor and indoor unit. Do not
connect the earth line to the gas tube, water pipe, lighting rod or the earth line of the telephone unit. Improper earthing may cause
electric shocks.
• When À nishing the refrigerant collection (pumping down), stop the compressor and then remove the coolant pipe. If you remove the refrigerant pipe while
the compressor is operating and the service valve is released, air is sucked and a pressure in the freezing cycle system will build up steeply, causing
an explosion or injury.
• When installing the unit, be sure to install the refrigerant pipe before starting the compressor.
If the refrigerant pipe is not installed and the compressor is operated with the service valve released, air is sucked and the pressure level of the refrigeration
cycle may increase abnormally which could result in a rupture and injury.
CAUTION
• A circuit breaker must be installed in the house distribution box for the direct connected power supply cables to the outdoor unit. In case of other
installations a main switch with a contact gap or more than 3mm has to be installed. Without a circuit breaker, the danger of electric shock exists.
• Do not install the unit near a location where there is Á ammable gas. The outdoor unit may catch À re if Á ammable gas leaks around it.
• Please ensure smooth Á ow of water when installing the drain hose. Improper installing may wet your furniture.
• An IEC approved power cord should be used. Power cord type: NYM.
1
Please mount the outdoor unit on stable ground to prevent vibration and increase of noise level.
Decide the location for piping after sorting out the different types of pipe available.
When removing side cover, please pull the handle after undoing the hook by pulling it downward. Reinstall the side
cover in reverse order of the removal.
CAUTION
• Do not touch the suction port, bottom surface, or aluminium À n of the outdoor unit.
• Failure to do so may cause an injury.
Please remove side cover
when connecting the piping
Please face this side (suction side)
Please face this side (suction
and connecting cord.
of the unit to the wall.
side) of the unit to the wall.
Please remove terminal
cover when connecting the
piping and connecting cord.
RAC-25NX2
RAC-35NX2 / RAC-50NX2
Condensed water disposal of outdoor unit
• There is holes on the base of outdoor unit for condensed water to exhaust.
• In order to Á ow condensed water to the drain, the unit is installed on a stand or a block so that the unit is 100mm above
the ground as shown À gure. Join the drain pipe to one hole.
• Cover the drain hole with a bush. To install the bush, put it on the drain hole as shown in the À gure and press the both
sides of the bush to À t into the hole. After installation, check whether the drain pipe and bush cling to the base À rmly.
Base
Base
Above 100mm
Above 100mm
Drain hole
Drain hole
Drain pipe
Outer diameter:
16mm or more
Outer diameter: 16mm
RAC-25NX2
RAC-35NX2
Base
Above 100mm
Drain hole
Bush
Drain pipe
Outer diameter: 16mm
RAC-50NX2
• Install the outdoor unit horizontally and make sure that condensate drains away.
• In case of using in cold weather area
Especially when there are heavy snows in cold weather area, condensed water freezes on the base and may not drain.
In this case, please remove the bush and the drain pipe at the bottom of the unit (left and centre near discharge portion
of air, each 1 place) to restore smooth drainage. Ensure that the distance from the drain hole to the ground is 250mm
or more.
< S878 : A >
3
THE CHOICE OF MOUNTING SITE
(Please note the following matters and obtain permission from customer before installation.)
WARNING
• The outdoor unit must be mounted at a location which can support heavy weight. Otherwise, noise and vibration will increase.
CAUTION
• Do not expose the unit under direct sunshine or rain. Besides, ventilation must be good and clear of obstruction.
• The air blown out of the unit should not point directly to animals or plants.
• The clearances of the unit from top, left, right and front are speciÀ ed in À gure below. At least two of the above sides must be open air.
• Be sure that the hot air blown out of the unit and noise do not disturb the neighbourhood.
• Do not install at a location where there is Á ammable gas, steam, oil and smoke.
• The location must be convenient for water drainage.
• Place the outdoor unit and its connecting cord at least 1m away from the antenna or signal line of television, radio or telephone. This
Vacuum Pump Adapter
is to avoid noise interference.
Names of Components
Dimensions of Mounting Stand of the Outdoor Unit
No.
Item
Qty
RAC-25NX2
Bush
(RAC-35NX2)
1
Mounting Stand
1
45
(RAC-50NX2)
2
Drain Pipe
2
1
12
30
500
100
(unit : mm)
above 200mm
(
)
above 50 mm when
* B
installed on the
ceiling of balcony
above 100mm
above 200mm
* A
(This À gure is RAC-50NX2)
For outdoor unit installation, allow at least 2 sides of
space around the unit to ensure ventilation Á ue.
* give clearance as wide as possible
2
1. Preparation of pipe
• Use a pipe cutter to cut the copper pipe and remove burr.
Copper pipe
CAUTION
• Remove burr and jagged edge will cause leakage.
• Point the side to be trimmed downwards during trimming to prevent copper chips from entering the pipe.
• Before Á aring, please put on the Á are nut.
• Please use exclusive tool for refrigerant R410A.
Pull downward
Die
Die
Outer diameter (ø)
A (mm) Rigid Flaring Tool
For R410A tool
6.35 (1/4")
0 – 0.5
9.52 (3/8")
0 – 0.5
12.7 (1/2")
0 – 0.5
2. Pipe connection
CAUTION
• In case of removing Á are nut of a indoor unit, À rst remove a nut of small diameter side, or a seal cap of big diameter
side will Á y out. Free from water into the piping when working.
Bush
• Be sure to tighten the Á are nut to the specÀ ed torque with a torque wrench. If the Á are nut is overtightened, the nut may
be split after a long period has passed, and may cause a refrigerant leak.
Drain pipe
• Please be careful when bending the copper pipe.
• Screw in manually while adjusting the center.
After that, use a torque wrench to tighten the connection.
Outer diameter
of pipe (ø)
Small diameter side
6.35 (1/4")
9.52 (3/8")
Large diameter side
12.7 (1/2")
Small diameter side
6.35 (1/4")
Valve head cap
9.52 (3/8")
Large diameter side
12.7 (1/2")
Valve core cap
4
3. Remove of air from the pipe and gas leakage inspection
Procedures of using vacuum pump for air removal
Remove the cap of valve core. Then, connect
the charge hose. Remove the cap of valve
1
head. Connect the vacuum pump adapter to the
vacuum pump and connect the charge hose to the
adapter.
Fully tighter the "Hi" shuttle of the manifold valve
and completely unscrew the "Lo" shuttle. Run
the vacuum pump for about 10-15 minutes, then
completely tighten the "Lo" shuttle and switch off
2
the vacuum pump.
• Loosen the spindle of the service valve with
RAC-35NX2 / RAC-50NX2
small diameter by 1/4 turn and tighten the spindle
Mounting Stand
immediately after 5 to 6 seconds.
50
• Remove the charging hose from the service
valve.
12
35
500
125
Completely unscrew the spindle of the service valve
3
(at 2 places) in anticlockwise direction to allow the
Á ow of refrigerant (using Hexagonal Wrench key).
Tighten the cap of valve head. Check the cap's
4
periphery if there is any gas leakage. The task is
then completed.
• The refrigerating machine oil is easily affected by moisture. Use caution
to prevent water from entering the cycle.
The body of service valve
• The difference in height between the indoor and outdoor unit should
be kept below 10m.
• The connecting pipe, no matter big or small, should all be insulated
with insulation pipe and then wrapped with vinyl tape. (The insulator
Cap of valve core
will deteriorate if it is not wrapped with tape.)
Cap of valve head
The connection of insulated drain hose.
Hexagonal wrench key
Inner diameter ø16mm
Please use insulated drain hose for the indoor
piping (commer cial product).
RAC-25NX2
RAC-35NX2
RAC-50NX2
Gas leakage inspection
A
above 400mm
above 300mm
above 200mm
Please use gas leakage detector to check if leakage occurs at connection of Flare nut as shown
B
above 150mm
above 50mm
above 50mm
on the right.
If gas leakage occurs, further tighten the connection to stop leakage.
Wiring of the outdoor unit
Please remove the side cover for wire connection.
Trimming tool
• If you cannot attach the side plate due to the connection cord, please press the connecting cord in the direction to the front
panel to À x it.
• Be sure that the hooks of the side cover À xed in certainly. Otherwise water leakage may occur and this causes short circuit
or faults.
• The connecting cord should not touch to service valve and pipes. (It becomes high temperature in heating operation.)
Checking for the electric source and the voltage range
• Before installation, the power source must be checked and necessary wiring work must be completed. To make the wiring
capacity proper, use the wire gauge list below for the wiring from house distribution fuse box to the outdoor unit in consideration
of the blocked rotor current.
IMPORTANT
A
Wire length
Wire gauge
up to 6m
up to 15m
Copper pipe
L, N
up to 20m
up to 6m
C, D
up to 20m
For R22 tool
1.0
1.0
L(A) N(B) C D
1.0
Cover
Earth terminal
RAC-25NX2
Cover
Flare nut
Wrench
Torque wrench
Torque N·m
(kgf·cm)
13.7 – 18.6 (140 – 190)
Earth terminal
34.3 – 44.1 (350 – 450)
RAC-50NX2
44.1 – 53.9 (450 – 550)
• Investigate the power supply capacity and other electrical conditions at the installing location.
19.6 – 24.5 (200 – 250)
• Depending on the model of room air conditioner to be installed, request the customer to make arrangements for the necessary
19.6 – 24.5 (200 – 250)
electrical work etc.
29.4 – 34.3 (300 – 350)
• The electrical work includes the wiring work up the outdoor unit. In localities where electrical conditions are poor, use of a
12.3 – 15.7 (125 – 160)
voltage regulation is recommended.
• Install outdoor for the room air conditioner within the reaching range of the line cord.
When the meter reaches -101KPa
(-76cmHg) during pumping fully
tighten the shuttle.
Meter showing
pressure
Closed
Charge hose
R410A Manifold valve
Vacuum pump
Valve
Vacuum pump adapter
When pumping starts, slightly loosen
Valve
the Á are nut to check of air sucked in.
Then tighten the Á are nut.
RAC-25NX2
When the meter reaches -101KPa
(-76cmHg) during pumping fully
tighten the shuttle.
Meter showing pressure
Closed
R410A Manifold valve
Charge hose
Vacuum pump
Valve
Vacuum pump adapter
When pumping starts, slightly loosen
Valve
the Á are nut to check of air sucked in.
Then tighten the Á are nut.
Cap of valve head
RAC-35NX2 / RAC-50NX2
5
WARNING
1.5mm
2
2.5mm
2
2
4.0mm
1.5mm
2
2.5mm
2
L(A) N(B) C
D
Cover
Earth terminal
L(A) N(B) C D
RAC-35NX2
When putting two connecting cords through the band.
IMPORTANT
Screw
Insulating plate
Fuse Capacity
Cord band
16A time delay fuse
Connecting cord
7
THIS APPLIANCE MUST BE EARTHED.
WARNING
Procedures of wiring
Indoor unit
Outdoor unit
Connecting cord
AC 220–230V
1ø 50Hz
Detail of cutting the connecting cord
• Outdoor unit
RAC-25NX2
50mm
50mm
C, D
10mm
L, N
10mm
Green + Yellow
Green + Yellow
Strip wires
RAC-35NX2 / RAC-50NX2
160mm
160mm
10mm
L, N
10mm
C, D
Strip wires
Green + Yellow
Green + Yellow
20mm
20mm
100mm
100mm
WARNING
• The naked part of the wire core should be 10mm À x it to the terminal tightly. Then try to pull the individual wire to
check if the contact is tight. Improper insertion may burn the terminal.
• Be sure to use only wire speciÀ ed for the use of air-conditioner.
• Please refer to the manual for wire connection and the wiring technique should meet the standard of the electrical
installation.
• Leave some space in the connecting cord for maintenance purpose and be sure to secure it with the
cord band.
• Secure the connecting cord along the coated part of the wire using the cord band. Do not exert pressure
on the wire as this may cause overheating or À re.
6
1. Operation test
• Please ensure that the air conditioner is in normal operating condition during the operation test.
• Explain to your customer the proper operation procedures as described in the user's manual.
• If the indoor unit does not operate, check to see that the connections are correct.
• Turn on the lamp in the room where the indoor unit is installed and check the remote controller for normal operation.
Insulation and maintenance of pipe connection
• The connected terminals should be completed sealed with heat insulator and
OUTSIDE
Sleeve of
then tied up with rubber strap.
protection pipe
• Please tie the pipe and power line together with vinyl tape as shown in the
À gure showing the installation of Indoor and outdoor units. Then À x their position
with holders.
• To enhance the heat insulation and to prevent water condensation, please
cover the outdoor part of the drain hose and pipe with insulation pipe.
• Completely seal any gap with putty.
Putty
Force-cooling operation
• When the service switch of the outdoor unit is pressed for 1 or more seconds, the force-cooling operation starts. Use
this mode when performing the failure diagnosis or collecting refrigerant into the outdoor unit.
Screw
Screw
Please remove side cover.
Cover
Service switch (If the switch is
Service switch (If the switch is pressed
pressed for more than 1 second,
for more than 1 second, the force-
the force-cooling operation
cooling operation starts. If the switch
starts. If the switch is pressed
is pressed for additional more than 1
for additional more than 1
second, the operation stops.)
second, the operation stops.)
RAC-35NX2 / RAC-50NX2
RAC-25NX2
CAUTION
Do not operate the unit for more than 5 minutes while the spindle of the service valve is closed.
8
INSIDE
Putty

Werbung

loading

Inhaltszusammenfassung für Hitachi RAC-25NX2

  • Seite 1 When the meter reaches -101KPa CAUTION (-76cmHg) during pumping fully HITACHI SPLIT UNIT AIR CONDITIONER the charge hose. Remove the cap of valve tighten the shuttle. • Do not expose the unit under direct sunshine or rain. Besides, ventilation must be good and clear of obstruction.
  • Seite 2: Nur Für Wartungpersonal

    Aussengerät Erforderliche Werkzeuge den Zuführschlauch anschließen. Den Deckel AUFGETEILTE KLIMAANLAGE VON HITACHI • Das Gerät nicht direkter Sonnenstrahlung oder Regen aussetzen. Außerdem muß für gute Belüftung und Hindernisfreiheit gesorgt ( M a r k i s t e i n We r k s t ü c k e x k l u s i v f ü r R 4 1 0 A ) vom Ventilkopf abnehmen.
  • Seite 3: Appareil D'extérieur

    Procédures de câblage fonctionnement de l’appareil. Comme illustré ci-contre, retirez le capuchon du (-76 cmHg) pendant le pompage, serrez CLIMATISEUR A DEUX BLOCS HITACHI noyau de vanne. Puis, raccordez le tuyau de charge. ATTENTION à fond le sélecteur. Appareil d’intérieur Appareil d’extérieur...
  • Seite 4: Precauzioni Di Sicurezza

    Procedure di collegamento prodotto correttamente. Rimuovere il cappuccio spillo della valvola. Quindi Quando il manometro raggiunge -101KPa (-76cmHg) durante HITACHI CONDIZIONATORE D’ARIA CON DUE CAUTELA collegare il Á essibile di carica. Rimuovere il cappuccio il pompaggio, stringere completamente il dado.
  • Seite 5: Sólo Para Personal Cualificado

    A continuación, Cuando el medidor alcance -101KPa (-76cmHg) HITACHI MANUAL DE INSTALACIÓN DE PRECAUCIÓN durante el bombeo, apriete del todo el manguito. conecte la manguera de carga. Retire el tapón de...
  • Seite 6: Medidas De Precaução

    Fechado • Broca Eléctrica ø65mm • Chave Inglesa Hexagonal ( • CertiÀ que-se de que o ar quente soprado da unidade e o ruído não perturbam a vizinhança. RAC-25NX2 4mm) • Porcas (14,17,19, 22mm) Detector de Fugas de Gás Mangueira •...
  • Seite 7 Û¯ÂÙÈο Ì ÙË ÛˆÛÙ‹ ÂÁηٿÛÙ·ÛË. AÊ·ÈÚ¤ÛÙ ÙÔ Î·¿ÎÈ ÙÔ˘ ÛÙÂϤ¯Ô˘˜ Ù˘ ‚·Ï‚›‰·˜. ¢È·‰Èηۛ· ËÏÂÎÙÚÈ΋˜ ηψ‰›ˆÛ˘ ŸÙ·Ó Ô ÌÂÙÚËÙ‹˜ ‰Â›ÍÂÈ -101KPa (-76cmHg) ηٿ ÙË ÏÂÈÙÔ˘ÚÁ›· HITACHI ∫§πª∞Δπ™Δπ∫√ ¢π∞πƒ√Àª∂¡√À ªÂÙ¿, Û˘Ó‰¤ÛÙ ÙÔ ÛˆÏ‹Ó· Ï‹ÚˆÛ˘. ∞Ê·ÈÚ¤ÛÙ ¶ƒ√™√Ã∏ Ù˘ ·ÓÙÏ›·˜ ÎÂÓÔ‡, ÛÊ›ÍÙ ÙÂÏ›ˆ˜ ÙË ‰È·‰ÚÔÌ‹.

Diese Anleitung auch für:

Rac-50nx2Rac-35nx2