Herunterladen Inhalt Inhalt Diese Seite drucken

Overload Indicator - Conrad 13 04 35 Bedienungsanleitung

Vorschau ausblenden Andere Handbücher für 13 04 35:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Attention!
Use suitable voltage-stable installation cables as instrument
or supply leads, with a cross-section of not more than max.
0.5 sq.mm, in order to avoid short-circuits at the soldered
connections with adjacent soldering eyes.
5.3 Commissioning
Before first commissioning, ensure that the unit is adequately
insulated and that air and creep distances are observed in accor-
dance with VDE 410 or VDE 1010 and IEC-1-1. Connect a control-
led (stabilised) voltage of 9 VDC (DC = direct voltage) to the sup-
ply input, ensuring that you observe the correct polarity ("+" and
"-").
Attention!
Simultaneous supply of the measuring device and measurement
of the current consumption is not possible with this unit. The
control cabinet, the tableau or similar housing must always
remain closed while the panelmeter is being operated.
In order to ensure relatively problem-free use/operation, avoid
- excessive temperature variations,
- high air humidity,
- strong vibrations,
- excessive ambient temperatures,
- the proximity of active generators, strong magnetic (louds-
peakers), electromagnetic (motors, transformers, relay trans-
mitters) and static (charges/discharges) fields, as all the above-
mentioned points can lead to an unstable display or to exces-
sive measurement errors.
10
Attention!
The measuring device/unit must be disconnected from the mea-
suring and supply circuit (9 V), before you change settings in
accordance with 5.1.
5.4 Direct current measurement (DCA)
Switch the measuring circuit on and observe the panelmeter dis-
play. The symbol "-" appears before the measured value in the
display, then a negative voltage is indicated (or the polarity of
the instrument leads is switched).
Attention!
1. Never exceed the max. permissible inputvalues. Depending on
the position of the solder bridges at the rear of the panelme-
ter these are 200 uADC, 2 mADC, 20 mADC, 200 mADC or 2
ADC.
2. Use caution with voltages exceeding 25 VAC or 35 VDC. Do
not touch any circuits or circuit components in which voltages
greater than 25 VAC or 35 VDC occur or may occur.

5.5 Overload indicator

If the measured voltage exceeds the max. permissible inputva-
lues, or if a measuring range is exceeded, instead of a measured
value a "1" appears or, with negative symbols, a "-1" in the dis-
play for overload, with the decimal point and the unit of measu-
rement adjusted accordingly.
5.6 Maintenance
The panelmeter is maintenance-free, apart from occasional clea-
ning of the display window. Use a clean, lint-free, anti-static, dry
cloth for cleaning.
11

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis