Herunterladen Inhalt Inhalt Diese Seite drucken

Bender ISOMETER isoUG425 Kurzanleitung Seite 36

Isolationsüberwachungsgerät
Vorschau ausblenden Andere Handbücher für ISOMETER isoUG425:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Connection
Connection type................................................................................................................................Push-wire terminal
Nominal current....................................................................................................................................................≤ 10 A
Conductor sizes .............................................................................................................................................AWG 24-14
Stripping length ....................................................................................................................................................10 mm
Rigid......................................................................................................................................................... 0.2...2.5 mm²
Flexible without ferrules ....................................................................................................................... 0.75...2.5 mm²
flexible with ferrules, with/without plastic collar................................................................................ 0.25...2.5 mm²
Multiple conductor, flexible withTWIN ferrule with plastic sleeve ....................................................... 0.5...1.5 mm²
Opening force........................................................................................................................................................... 50 N
Test opening, diameter....................................................................................................................................... 2.1 mm
Other
Operating mode ........................................................................................................................... Continuous operation
Mounting..................................................................................................... Cooling slots must be ventilated vertically
Degree of protection, built-in components (DIN EN 60529) ................................................................................. IP30
Degree of protection, terminals (DIN EN 60529) ................................................................................................... IP20
Enclosure material .................................................................................................................................... Polycarbonate
DIN rail mounting acc. to................................................................................................................................. IEC 60715
Screw fixing ......................................................................................................................... 2 x M4 with mounting clip
Weight.................................................................................................................................................................≤ 150 g
Bender GmbH & Co. KG
Londorfer Str. 65 • 35305 Grünberg • Germany
Postfach 1161 • 35301 Grünberg • Germany
Tel.: +49 6401 807-0
Email: info@bender.de
Web: http://www.bender.de
36
Fax: +49 6401 807-259
isoUG425_D00220_02_Q_DEEN / 05.2018