Gamma instabus
AP 251/11 Bewegungsmelder IP55
AP 251/11 Motion detector IP55
AP 251/21 Bewegungsmelder IP55
AP 251/21 Motion detector IP55
5WG1 251-3AB11 (titanweiß)
5WG1 251-3AB11 (titanium white)
5WG1 251-3AB21 (anthrazit)
5WG1 251-3AB21 (anthracite)
Bedien- und Montageanleitung
Operating and Mounting Instructions
Stand: Mai 2008
Issued: May 2008
Bild / Figure 1
Bild / Figure 2
Bild / Figure 3
Bild / Figure 4
A5E01251127C DS02
D
Produkt- und Funktionsbeschreibung
Der Bewegungsmelder IP55 (Kurzbezeichnung AP 251/_1) ist
ein Aufputzgerät mit integrierter KNX-Schnittstelle zur Montage
an einer Wand oder Decke (siehe Bild 1) im Innen- oder Außen-
bereich. Er detektiert passiv die Wärmestrahlung von Körpern in
seinem Erfassungsbereich. Für Beginn und Ende erkannter Be-
wegungen ist getrennt einstellbar, ob EIN oder AUS über den
Bus zu melden sind und ob ein weiteres Telegramm zusätzlich
zu übertragen ist. Auf Grund des großen Erfassungsbereichs von
290° ist der Bewegungsmelder auch zur Montage auf einer 90°-
Außenecke geeignet. Hierzu ist ein spezieller Montagesockel als
Zubehör erhältlich (titanweiß: 5TC7 900, anthrazit: 5TC 901).
Unter Verwendung einer ebenfalls als Zubehör (5TC7 902) er-
hältlichen Infrarot-Fernbedienung kann der Anwender über den
in den Bewegungsmelder integrierten IR-Empfänger sowohl die
Betriebsart (Testbetrieb, helligkeitsabhängiger oder helligkeit-
sunabhängiger Betrieb, Standardbetrieb, Impulsbetrieb) als
auch Helligkeitsschwelle und Nachlaufzeit des Melders bequem
selber einstellen.
Die Werkseinstellung der Betriebsart im Auslieferzustand ist ei-
ne helligkeitsabhängige Bewegungserkennung mit einem Hel-
ligkeitswert von 7 Lux und einer Nachlaufzeit von 2 Minuten.
Die Stromversorgung der Melderelektronik erfolgt über die Bus-
spannung.
Weitere Informationen
http://www.siemens.de/gamma
Technische Daten
Sensor
• Erfassungsbereich: 290°
• Montagehöhe:
2 – 4 m, ideal 2,50 m
• Reichweite (Montagehöhe 2,50 m, +22 °C): ca. 16 m
• Dämmerungssensor: 0,5 – 2000 Lux
• Nachlaufzeit : 5 Sekunden – 30 Minuten
• Impulsbetrieb 1 s EIN , 9 s AUS
• Test-Modus: Helligkeitsunabhängiger Betrieb,
Nachlaufzeit 2 s
Spannungsversorgung
• Busspannung: erfolgt über die Buslinie
• Busstrom: 11 mA
A2
Anschlüsse
• Busleitung: Busklemme schraubenlos,
0,6... 0,8 mm ∅ eindrahtig, Abisolierlänge 5 mm.
Mechanische Daten
Abmessungen: ca. 180 mm x 86 mm x 74 mm (L x B x H)
Verstellbereich Schwenkarm: max. 120°
Gewicht: ca. 245 g
Elektrische Sicherheit
Schutzart (nach EN 60529): IP55
A1
Umweltbedingungen
• Umgebungstemperatur im Betrieb: - 25 ... + 50 °C
• Lagertemperatur: - 25 ... + 70 °C
• rel. Feuchte (nicht kondensierend): 5 ... 93 %
Prüfzeichen
KNX EIB
Lage und Funktion der Anzeige- und Bedienelemente
Siehe Bild 2 (Anschluss-Leiterplatte des Bewegungsmelders)
A1 Taste zum Umschalten zwischen Normalmodus und Adres-
siermodus zur Übernahme der physikalischen Adresse.
A2 LED zur Anzeige Normalmodus (LED Aus) oder Adressier-
modus (LED Ein); sie erlischt automatisch nach Übernah-
me der physikalischen Adresse.
siehe Bild 3 (Sensorseite des Bewegungsmelders)
S1 Bedientaste S1
S2 Bedientaste S2
Montage und Verdrahtung
Montageort
Zur optimalen Bewegungsdetektion sollte der Bewegungsmel-
der seitlich zur Gehrichtung montiert werden (siehe Bild 4),
möglichst in einer Höhe von 2,5 m, nicht über sondern mög-
lichst unter einer Leuchte und mit mindestens 0,5 m Abstand zu
einer Leuchte im Erfassungsbereich.
Erfassungsbereich
Um ein unerwünschtes Ansprechen des Bewegungsmelders zu
vermeiden, ist auf potentielle Störquellen (wie z.B. Warmluft-
strömungen, bewegte Sträucher oder Bäume) zu achten. Uner-
wünschte Erfassungsbereiche können durch Anbringen der mit-
gelieferten Abdeckblende bei Bedarf ausgeblendet werden.
Hierzu ist sie entsprechend auszuschneiden. Der Fixierungsring
der Abdeckblende darf beim Ausschneiden der Segmente nicht
durchtrennt werden (siehe Bild 5). Durch die Blende abgedeckte
Linsenbereiche erfassen keine Bewegungen.
Der Erfassungsbereich des Melders kann außerdem durch Dre-
hen der Linse um +/- 30° nach rechts oder links verändert wer-
den. Die Erfassungsreichweite kann durch Verstellen des
Schwenkarms verändert werden (siehe Bild 6).
Montage und Anschließen der Busleitung
Der Anschlusskasten des Bewegungsmelders ist bei der Wand-
montage lagerichtig (TOP oben, siehe Bild 7 und Bild 8) zu be-
festigen. Hierzu können die mitgelieferten Dübel und Schrau-
ben verwendet werden. Der Abstand der Bohrungen im An-
schlusskasten ist zur Befestigung auf einer 60 mm UP-Dose ab-
gestimmt. Die Busleitung ist durch eine der Durchstoßöffnun-
gen in den Anschlusskasten einzuführen. Die Isolierung der ro-
ten und der schwarzen Ader ist ca. 5 mm weit zu entfernen, die
Adern sind in den jeweils gleichfarbigen Teil der Busklemme zu
stecken, und anschließend ist die Busklemme in ihre Halterung
auf der Anschluss-Leiterplatte des Melders zu stecken.
Seite 1 von 2
GB
Product and Applications Description
The IP55 motion sensor (short title AP 251/_1) is a surface
mounted device with integrated KNX interface for mounting on
a wall or ceiling (see figure 1) in inside or outside areas. It
works by passive detection of heat radiated by bodies in its cap-
ture zone. It can be set separately for the beginning and end of
detected movements, whether these are to be reported over
the bus and whether a further telegram is also to be sent. Ow-
ing to its large capture zone of 290°, the motion sensor is also
suitable for mounting on a 90° outside corner. A special mount-
ing base is available for this purpose as an accessory (5TC7 900
in titanium white and 5TC 901 in anthracite).
By using an infrared remote control which is also available as an
accessory (5TC7 902), a user can conveniently set, by means of
the IR receiver incorporated in the motion sensor, as well the
detector's mode (test mode, brightness-dependent or bright-
ness-independent mode, standard mode, pulsed mode) as the
brightness threshold and the delay time, independently.
The factory setting of the mode in the as-delivered state is
brightness-dependent motion detection with a brightness
threshold of 7 lux and a delay time of 2 minutes.
The detector electronics are powered via the bus voltage.
Additional Information
http://www.siemens.com/gamma
Technical Specifications
Sensor
• Capture zone: 290°
• Mounting height: 2 – 4 m, ideally 2.50 m
• Range (mounting height 2.50 m, +22°C): approx. 16 m
• Dawn/twilight sensor: 0.5 - 2000 Lux
• Delay time
5 seconds - 30 minutes
• Pulse mode
1 second ON, 9 seconds OFF
• Test mode:
Brightness-independent mode,
after-run time 2 seconds
Power supply
• Bus voltage: via bus line
• Bus current: 11 mA
Connections
• Bus cable: screwless bus terminal,
0.6... 0.8 mm ∅ single-core, insulation strip length 5 mm.
Mechanical specifications
Dimensions:: approx. 180 mm × 86 mm × 74 mm (L × W × H)
Tilting arm adjustment zone: max. 120°
Weight: approx. 245 g
Electrical safety
Degree of protection (to EN 60529): IP55
Environmental specifications
• Ambient temperature in operation: - 25 ... + 50°C
• Storage temperature: - 25 ... + 70°C
• Relative humidity (non-condensing): 5 ... 93%
Markings
KNX EIB
Location and Function of the Display and Operating Elements
See figure 2 (Motion detector printed connection board)
A1 Key for toggling between normal mode and addressing
mode for transferring the physical address.
A2 LED for indicating normal mode (LED Off) or addressing
mode (LED On); it is automatically extinguished once the
physical address has been transferred.
See figure 3 (motion detector sensor side)
S1 Operating key S1
S2 Operating key S2
Mounting and Wiring
Mounting site
For optimum motion detection, the motion detector should be
mounted sideways on to the direction of motion (see figure 4),
as far as possible at a height of 2.5 m, as far as possible not
over but under a luminaire and with at least 0.5 m separation
from any luminaire in the capture zone.
Capture zone
In order to avoid unwanted responses from the motion detec-
tor, you must consider potential sources of interference (such as
warm air flows, moving bushes or trees). Unwanted capture
zones can be filtered out as required by fitting the cover screen
supplied. It is to be cut out accordingly for this purpose. The
cover screen fixing ring must not be separated when cutting out
segments (see figure 5). No movements will be captured by ar-
eas of the lens covered by the cover screen.
The capture zone of the detector can also be altered by turning
the lens through some +/- 30° to the right or left. The capture
range can be changed by adjusting the tilting arm (see figure
6).
Mounting and connecting the bus cable
The motion detector's connection box must be correctly posi-
tioned when mounting on a wall (TOP showing, see figures 7
and 8). You can use the dowels and screws supplied for this.
The spacing of the drilled holes in the connection box is to be
matched on a 60 mm flush-mounted socket. The bus cable is to
be brought in through one of the punched out openings in the
connection box. The insulation of the red and black wire is to be
stripped back for approx. 5 mm, the wires are to be plugged
into the part of the bus terminal with the same colour and the
bus terminal is then to be plugged into its mounting on the de-
tector's printed connection board.
Page 1 of 2

Werbung

loading

Inhaltszusammenfassung für Siemens IP55 AP 251/11

  • Seite 1 Die Stromversorgung der Melderelektronik erfolgt über die Bus- The detector electronics are powered via the bus voltage. Bedien- und Montageanleitung spannung. Operating and Mounting Instructions Weitere Informationen Additional Information Stand: Mai 2008 http://www.siemens.de/gamma http://www.siemens.com/gamma Issued: May 2008 Technische Daten Technical Specifications Sensor Sensor • Erfassungsbereich: 290°...
  • Seite 2 • The operating instructions must be handed over to the client. • Ein defektes Gerät ist mit einer kurzen Fehlerbeschreibung • Any faulty devices should be returned to the local Siemens an die zuständige Geschäftsstelle der Siemens AG zu senden.

Diese Anleitung auch für:

5wg1 251-3ab11Ip55 ap 251/215wg1 251-3ab21