Set-up
3
1
4
5
4
5
1
2
6
1 Attachment holes
2
Connection PCB
3
Cover contacts
4
Pierce cable entries
5
Pull reliefs
Connection diagram
Flash lamp
Pressure chamber loudspeaker
+
-
+
12k1
6k04
10R
6k04
0R
12k1
Tamper
The cover contact in the housing is series connected with the cover
contact on the connection PCB.
Do not cut the cables too short when connecting.
To ensure that the tear-off protection functions correctly, the
cable connection should not be too taught.
(See above
tear-off protection)
6
Ensure that the cable loop between the pull relief and the
connection PCB is long enough.
Honeywell Security Group
Novar GmbH
Johannes-Mauthe-Straße 14
D-72458 Albstadt
www.honeywell.com/security/de
3
6
Tear-off protection
When the housing is screwed to the
wall the bolt on the back presses the
connection PCB in direction to the top
part of the housing. So the cover
contact is activated when the housing
is closed.
If the housing is torn off the wall, the
bolt moves back and the cover contact
triggers.
Monitored
Not monitored
-
-
Monitoring circuit
Cover contact
ST1
0V
Free soldering terminal
for Z wiring
P02203-10-002-08
2011-08-02
©2011 Novar GmbH
Connection of tamper detector group in Z wiring
12k1
6k04
Tamper detector group
1
The end-of-line resistor of the tamper detector group (12k1) must be in
5
the last device.
With a stub layout, 6k04 is linked at each end.
4
Final assembly
- Break off the selected cable entry and insert the included cable
sleeve into the opening.
- Secure the cable with a pull relief.
- In order to prevent leakage current, the connections must be coated
with a protective lacquer (also those which are not occupied).
Ensure that the leads are covered with a protective lacquer as far as
1
the insulation.
- Insert the reach-through protection.
Ensure that the gasket is not damaged.
- Attach the top part of the housing with the
radius pointing upward and screw tight.
Only tighten the screws
slightly (preferably by hand).
Do not use a cordless screwdriver with
uncontrolled torque. If the screws are
screwed too tight, the housing may be
damaged.
- Insert the seals in the screw openings.
Technical data
Flash lamp:
Rated operating voltage
Operating voltage range
Current consumption at U
Flashing frequency
Pressure chamber loudspeaker:
Volume
The actuation signal will be provided by
the connected control panel.
General data:
Environmental protection class as per VdS IV
Protection class as per DIN 40 050
Operating temperature range
Storage temperature range
Dimensions W x H x D
- 048700.17
- 048720.17
Color
Housing
Luminous field
Cover contact
12k1
10R
12 V DC
10 V to 15 V DC
400 mA
NORM
approx. 2 Hz
>100 dB(A)
IP 44
-25 °C to +60 °C
-25 °C to +70 °C
185 x 210 x 98 mm
185 x 315 x 98 mm
traffic white
(similar RAL 9016)
Red
Cover contact
6k04
10R
Radius