Herunterladen Inhalt Inhalt Diese Seite drucken

Control Box Positions; Positioning The Control Box In Air-Conditioning And Cold-Water Systems; Changing The Control Box Position - Grundfos ALPHA1 15-50 Bedienungsanleitung

Alpha1 serie
Vorschau ausblenden Andere Handbücher für ALPHA1 15-50:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

3.2 Control box positions

A
C
Fig. 2
Control box positions
Always install the pump with a horizontal motor shaft.
Pump installed correctly in a vertical pipe. See fig. 2, pos. A.
Pump installed correctly in a horizontal pipe. See fig. 2, pos. B.
Do not install the pump with a vertical motor shaft. See fig. 2,
pos. C and D.
3.2.1 Positioning of the control box in heating and domestic
hot-water systems
You can position the control box in position 3, 6 and 9 o'clock.
See fig. 3.
Fig. 3
Control box positions, heating and domestic hot-water
systems
3.2.2 Positioning the control box in air-conditioning and
cold-water systems
Position the control box with the plug pointing downwards. See
fig. 4.
Fig. 4
Control box position, air-conditioning and cold-water
systems
6
B
D

3.2.3 Changing the control box position

CAUTION
Hot surface
Minor or moderate personal injury
- Position the pump so that persons cannot
accidentally come into contact with hot surfaces.
CAUTION
Pressurised system
Minor or moderate personal injury
- Before dismantling the pump, drain the system or
close the isolating valve on either side of the
pump. The pumped liquid may be scalding hot and
under high pressure.
If you change the position of the control box, fill the
system with the liquid to be pumped or open the
isolating valves.
1
2
3
4
Fig. 5
Changing the control box position
You can turn the control box in steps of 90 °.
1. Remove the four screws.
2. Turn the pump head to the desired position.
3. Insert and cross-tighten the screws.

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis