ACXF60-60550
Air conditioner
MODEL NO. :-
Installation Instruction
CS-MZ20CFEA Series
CS-Z25, Z35, Z50CFEAW Series
Required tools for Installation Works
1 Phillips screw driver (bit length more than 210 mm)
2 Level gauge
3 Electric drill, hole core drill (ø70 mm)
4 Hexagonal wrench (4 mm)
5 Spanner
6 Pipe cutter
7 Reamer
8 Knife
QR code for
9 Gas leak detector
Web Manual
10 Measuring tape
11 Thermometer
https://eu.datanavi.ac.smartcloud.panasonic.com/documents/index.htm?model=CS-Z25CFEAW
•
Please scan the above matrix two-dimensional (2D) barcode and read thoroughly for the detailed instruction.
Panasonic will not be responsible for any accident or damage due to improper installation in anyway not described in the detailed manuals. Malfunction caused by incorrect
installation is also not covered by product warranty.
SAFETY PRECAUTIONS
•
Read the following "SAFETY PRECAUTIONS" carefully before installation.
•
This installation manual must be used together with another installation manual incorporated in applicable outdoor unit as complete full set of instructions.
•
Confi rm the type of gas used before installation.
•
Electrical work must be installed by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model to be installed.
•
The caution items stated here must be followed because these important contents are related to safety. The meaning of each indication used is as below.
Incorrect installation due to ignoring of the instruction will cause harm or damage, and the seriousness is classifi ed by the following indications.
WARNING
This indication shows the possibility of causing death or serious injury.
CAUTION
This indication shows the possibility of causing injury or damage to properties only.
The items to be followed are classifi ed by the symbols:
Symbol with white background denotes item that is PROHIBITED.
Symbol with dark background denotes item that must be carried out.
•
Carry out test running to confi rm that no abnormality occurs after the installation. Then, explain to user the operation, care and maintenance as stated in
instructions. Please remind the customer to keep the operating instructions for future reference.
WARNING
Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer. Any unfi t method or using incompatible material may cause product damage, burst
and serious injury.
Do not install outdoor unit near handrail of veranda. When installing air-conditioner unit on veranda of a high rise building, child may climb up to outdoor unit and cross over the handrail causing an
accident.
Do not use unspecifi ed cord, modifi ed cord, joint cord or extension cord for power supply cord. Do not share the single outlet with other electrical appliances. Poor contact, poor insulation or over current
will cause electrical shock or fi re.
Do not tie up the power supply cord into a bundle by band. Abnormal temperature rise on power supply cord may happen.
Do not insert your fi ngers or other objects into the unit, high speed rotating fan may cause injury.
Do not sit or step on the unit, you may fall down accidentally.
Keep plastic bag (packaging material) away from small children, it may cling to nose and mouth and prevent breathing.
When installing or relocating air conditioner, do not let any substance other than the specifi ed refrigerant, eg. air etc mix into refrigeration cycle (piping). Mixing of air etc. will cause abnormal high pressure
in refrigeration cycle and result in explosion, injury etc.
Do not pierce or burn as the appliance is pressurized. Do not expose the appliance to heat, fl ame, sparks, or other sources of ignition.
Else, it may explode and cause injury or death.
Do not add or replace refrigerant other than specifi ed type. It may cause product damage, burst and injury etc.
Do not use joint cable for indoor / outdoor connection cable. Use the specifi ed indoor/outdoor connection cable, refer to instruction 5 CONNECTING THE INDOOR/OUTDOOR CONNECTION CABLE and
connect tightly for indoor/outdoor connection. Clamp the cable so that no external force will have impact on the terminal. If connection or fi xing is not perfect, it will cause heat up or fi re at the connection.
•
For R32/R410A model, use piping, fl are nut and tools which is specifi ed for R32/R410A refrigerant. Using of existing (R22) piping, fl are nut and tools may cause abnormally high pressure in the
refrigerant cycle (piping), and possibly result in explosion and injury.
For R32 and R410A, the same fl are nut on the outdoor unit side and pipe can be used.
•
Since the working pressure for R32/R410A is higher than that of refrigerant R22 model, replacing conventional piping and fl are nuts on the outdoor unit side are recommended.
•
If reuse piping is unavoidable, refer to instruction "IN CASE OF REUSING EXISTING REFRIGERANT PIPING".
•
Thickness of copper pipes used with R32/R410A must be more than 0.8 mm (3/4 - 2.0HP). Never use copper pipes thinner than 0.8 mm (3/4 - 2.0HP).
•
It is desirable that the amount of residual oil less than 40 mg/10 m.
Engage authorized dealer or specialist for installation. If installation done by the user is incorrect, it will cause water leakage, electrical shock or fi re.
For refrigeration system work, install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electrical shock or fi re.
Use the attached accessories parts and specifi ed parts for installation. Otherwise, it will cause the set to fall, water leakage, fi re or electrical shock.
Install at a strong and fi rm location which is able to withstand weight of the set. If the strength is not enough or installation is not properly done, the set will drop and cause injury.
For electrical work, follow the national regulation, legislation and this installation instructions. An independent circuit and single outlet must be used. If electrical circuit capacity is not enough or defect found
in the electrical work, it will cause electrical shock or fi re.
Wire routing must be properly arranged so that control board cover is fi xed properly. If control board cover is not fi xed perfectly, it will cause fi re or electrical shock.
This equipment is strongly recommended to be installed with Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD), with sensitivity of 30 mA at 0.1 sec or less. Otherwise, it may cause
electrical shock and fi re in case of equipment breakdown or insulation breakdown.
During installation, install the refrigerant piping properly before running the compressor. Operation of compressor without fi xing refrigeration piping and valves at opened position will cause suck-in of air,
abnormal high pressure in refrigeration cycle and result in explosion, injury etc.
During pump down operation, stop the compressor before removing the refrigeration piping. Removal of refrigeration piping while compressor is operating and valves are opened will cause suck-in of air,
abnormal high pressure in refrigeration cycle and result in explosion, injury etc.
Tighten the fl are nut with torque wrench according to specifi ed method. If the fl are nut is over-tightened, after a long period, the fl are may break and cause refrigerant gas leakage.
After completion of installation, confi rm there is no leakage of refrigerant gas. It may generate toxic gas when the refrigerant contacts with fi re.
Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when the refrigerant contacts with fi re.
Be aware that refrigerants might not contain an odour.
This equipment must be properly earthed. Earth line must not be connected to gas pipe, water pipe, earth of lightning rod and telephone.
Otherwise, it may cause electrical shock in case of equipment breakdown or insulation breakdown.
CAUTION
Handle the unit surface with care to avoid scratching the surface by sharp or rough items (e.g. fi ngernails, tools, rings, etc). Wear hand gloves when performing installation work.
Do not install the unit in a place where leakage of fl ammable gas may occur. In case gas leaks and accumulates at surrounding of the unit, it may cause fi re.
Prevent liquid or vapor from entering sumps or sewers since vapor is heavier than air and may form suffocating atmospheres.
Do not release refrigerant during piping work for installation, re-installation and during repairing refrigeration parts. Take care of the liquid refrigerant, it may cause frostbite.
Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.
Do not touch the sharp aluminium fi n, sharp parts may cause injury.
Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the furniture.
Select an installation location which is easy for maintenance.
Incorrect installation, service or repair of this air conditioner may increase the risk of rupture and this may result in loss damage or injury and/or property.
Power supply connection to the room air conditioner.
Use power supply cord 3 x 1.5 mm² (3/4 ~ 1.5HP), 3 x 2.5 mm² (2.0HP) type designation 60245 IEC 57 or heavier cord.
Connect the power supply cord of the air conditioner to the mains using one of the following method.
Power supply point should be in easily accessible place for power disconnection in case of emergency.
In some countries, permanent connection of this air conditioner to the power supply is prohibited.
1) Power supply connection to the receptacle using power plug.
Use an approved 15/16 A (3/4 ~ 1.5HP), 16 A (2.0HP) power plug with earth pin for the connection to the socket.
2) Power supply connection to a circuit breaker for the permanent connection.
Use an approved 16 A (3/4 ~ 2.0HP) circuit breaker for the permanent connection. It must be a double pole switch with a minimum 3.0 mm contact gap.
Installation work.
It may need two people to carry out the installation work.
Keep any required ventilation openings clear of obstruction.
PRECAUTION FOR USING R32 REFRIGERANT
•
Pay careful attention to the following precaution points and the installation work procedures.
When connecting fl are at indoor side, make sure that the fl are connection is used only once, if torqued up and released, the fl are must be remade. Once the fl are connection was torqued up correctly and
leak test was made, thoroughly clean and dry the surface to remove oil, dirt and grease by following instructions of silicone sealant. Apply neutral cure (Alkoxy type) & ammonia-free silicone sealant that
is non-corrosive to copper & brass to the external of the fl ared connection to prevent the ingress of moisture on both the gas & liquid sides. (Moisture may cause freezing and premature failure of the connection)
The appliance shall be stored, installed and operated in a well ventilated room with indoor fl oor area larger than A
(m²) [refer Table A] and without any continuously operating ignition source. Keep away
min
from open fl ames, any operating gas appliances or any operating electric heater. Else, it may explode and cause injury or death.
Refer to "PRECAUTION FOR USING R32 REFRIGERANT" in outdoor unit installation manual for other precautions that need to pay attention to.
Accessory Parts
No.
Accessories part
Qty.
No.
Accessories part
Qty.
No.
Accessories part
Qty.
No.
Accessories part
Mounting plate
Insulation sheet
Battery
Remote control
holder fi xing screw
1
1
3
2
5
2
7
Screw (for Indoor
Remote Control
Remote control
unit/Mounting plate)
holder
2
11
4
1
6
1
(M4×25L)
• Required Material
R ead catalog and other technical materials and prepare the required materials.
Pipe Size Reducer (CZ-MA1PA) for CS-Z50*** when connect to multi.
• Other Items to be Prepared (Locally Purchased)
Product name
Remarks
Rigid PVC pipe
VP-20 (outer diameter ø26mm), VP-30 (outer diameter ø38mm), Reducer (VP-30 - VP-20) ; also socket, elbow and
other parts as neccessary.
Adhesive
PVC adhesive
Insulation
For drain piping insulation (foamed polyethylene with a thickness of 10mm or more)
Indoor/outdoor connecting cable
4 × 1.5mm
2
fl exible cord : type designation 60245 IEC57 (H05RN-F)
Table A
A
= (
/ (2.5 x ( LFL )
(5/4)
x h
2
m
))
** not less than concentration factor margin
min
c
0
Capacity W
Max. Refrigerant
Model
Indoor A
(m²)
min
A
= Required minimum room area, in m²
(HP)
Charge (kg)
min
m
= Refrigerant charge in appliance, in kg
c
MZ20***
3/4HP
Refer to Installation Instruction at outdoor unit
LFL = Lower fl ammability limit (0.307 kg/m³)
h
= Installation height of the appliance (0.6m for fl oor console)
0
Z25***
1.0HP
1.01
Not applicable (*)
CF = Concentration factor with a value of 0.75
Z35***
1.5HP
1.10
Not applicable (*)
** The required minimum room area, A
, shall also be governed by the concentration
min
factor margin formula below :
Z50***
2.0HP
1.47
Not applicable (*)
=
/ ( CF x
A
m
LFL
x h
)
(*) Systems with total refrigerant charge,
m
, lower than 1.84 kg are not subjected
min
c
0
c
to any room area requirements.
The higher value shall be taken when determining the room area.
* Table "A" only applicable for single split connection.
* In case of connection to outdoor multi inverter, refer to installation manual at
outdoor unit.
1. Selecting the Installation Location
• Indoor unit
Before choosing the installation site, obtain user approval.
There should not be any heat source or steam near the unit.
There should not be any obstacles blocking the air circulation.
A place where air circulation in the room is good.
A place where drainage can be easily done.
12 Megameter
A place where noise prevention is taken into consideration.
13 Multimeter
Do not install the unit near the door way.
14 Torque wrench
18 N•m (1.8 kgf•m)
Locate the indoor unit at least 1m or more from TV, radio, wireless equipment,
42 N•m (4.3 kgf•m)
antenna cables and fl uorescent light, and 2m or more away from a telephone.
55 N•m (5.6 kgf•m)
Ensure the spaces indicated by arrows from the wall, ceiling, fence or other
65 N•m (6.6 kgf•m)
100 N•m (10.2 kgf•m)
obstacles.
15 Vacuum pump
16 Gauge manifold
17 Hand gloves
3. Installing the Indoor Unit
I
Exposed
installation
N
Refrigerant piping
D
1) Drill a hole (70mm in diameter) in the spot indicated by the
symbol in the illustration as below.
O
2) The location of the hole is different depending on which side of the pipe is taken out.
3) For piping, see 4. Connecting the refrigerant piping.
4) Allow space around the pipe for a easier indoor unit pipe connection .
O
Wall
(Unit : mm)
R
Left bottom piping
80
70
Right bottom piping
Left/right side piping
35
U
Left back piping
80
70
Right back piping
N
I
CAUTION
Min. allowable length
T
• The suggested shortest pipe length is 3.0m, in order to avoid noise from the outdoor unit and vibration.
(Mechanical noise and vibration may occur depending on how the unit is installed and the environment in which it is used.)
• See the installation manual for the outdoor unit for the maximum pipe length.
• For multi-connections, see the installation manual for the multi-outdoor unit.
To drill a hole in the wall and install a sleeve of piping
1) Insert the piping sleeve to the hole.
Indoor
2) Fix the bushing to the sleeve.
3) Cut the sleeve until it extrudes about 15 mm from the wall.
CAUTION
Sleeve
(Locally
When the wall is hollow, please be sure to use the sleeve for tube
purchased)
ass'y to prevent dangers caused by mice biting the connecting cable.
4) Finish by sealing the sleeve with putty or caulking
compound at the fi nal stage.
Drain piping
ø70 through hole
1) Use commercial rigid polyvinyl chloride pipe (general VP-20 pipe, outer diameter 26mm, inner diameter
20mm) for the drain pipe.
2) The drain hose (outer diameter 18mm at connecting end, 270mm long) is supplied with the indoor unit.
Prepare the drain pipe picture below position.
3) The drain pipe should be inclined downward so that water will fl ow smoothly without any accumulation.
(Should not be trap.)
4) Insert the drain hose to this depth so it won't be pulled out of the drain pipe.
5) Insulate the indoor drain pipe with 10mm or more of insulation material to prevent condensation.
6) Remove the air fi lters and pour some water into the drain pan to check the water fl ows smoothly.
In case back piping
105
Refrigerant pipe
Drain hose
at below
100
270
Drain hose
50mm
or more
(Unit: mm)
Reducer
Insert drain hose
Vinyl chloride
to this depth so it
Vinyl chloride
drain pipe
drain pipe
won't be pulled
(VP-30)
(VP-20)
out of drain pipe.
CAUTION
Use polyvinyl chloride adhesive agent for gluing. Failure to do so may cause water leakage.
4. Connecting the Refrigerant Piping
Connecting The Piping to Indoor
For connection joint of all models
Additional Precautions For R32 Models when connecting by fl aring at indoor side
Please make flare after inserting
Ensure to do the re-fl aring of pipes before connecting to units to avoid leaking.
flare nut (locate at joint portion of
tube assembly) onto the copper
Seal suffi ciently the fl are nut (both gas and liquid sides) with neutral cure (Alkoxy type) &
pipe. (In case of using long piping)
ammonia-free silicone sealant and insulation material to avoid the gas leak caused by freezing.
Connect the piping
Apply neutral cure
•
Align the center of piping and
(Alkoxy type) and
ammonia-free silicone
suffi ciently tighten the fl are nut
sealant along the
with fi ngers.
•
Further tighten the fl are nut with
torque wrench in specifi ed torque
as stated in the table.
Neutral cure (Alkoxy type) & ammonia-free silicone sealant is only to be applied after
Spanner or
pressure testing and cleaning up by following instructions of sealant, only to the outside
Wrench
Torque
of the connection. The aim is to prevent moisture from entering the connection joint and
wrench
possible occurrence of freezing. Curing sealant will take some time. Make sure sealant
will not peel off when wrapping the insulation.
Connecting The Piping to Outdoor
Decide piping length and then cut by using pipe cutter.
Remove burrs from cut edge.
Make fl are after inserting the fl are nut (locate at valve) onto the copper pipe. Align
center of piping to valve and then tighten with torque wrench to the specifi ed torque
Qty.
as stated in the table.
Connecting The Piping to Outdoor Multi
2
Decide piping length and then cut by using pipe cutter. Remove burrs from cut edge.
Make flare after inserting the flare nut (locate at valve) onto the copper pipe. Align
center of piping to valve and then tighten with torque wrench to the specified torque
as stated in the table.
5. Connecting the Indoor/Outdoor Connection Cable
1
Guide connection cable pass through refrigerant piping port and lead the connection cable into the control box.
2
Check the color of the wires on the terminal board and secure them with screws.
3
Secure the connection cable with cord holder.
4
Guide and push the connection cable inside so that it does not apply undue force on the front grille.
5
Fix the connection cable into cable holder.
CAUTION
When the wall is hollow, please be sure to use the sleeve for tube ass'y to prevent dangers caused by mice biting the connection cable.
•
Connection cable between indoor unit and outdoor unit should be approved
polychloroprene sheathed 4 x 1.5 mm
2
fl exible cord, designation type 60245
IEC 57 (H05RN-F) or heavier cord. Allowable connection cable length of each
indoor unit shall be 30 m or less.
•
Ensure that the terminal numbers on the indoor unit are connected to the
same terminal numbers on the outdoor unit by the right coloured wires
as shown in the diagram.
•
Earth lead wire should be longer than the other lead wires as shown in
the diagram for electrical safety purpose in case the cord slips out from
the anchorage.
Refrigerant piping port
•
Secure the cable onto the control board with the holder (clamper).
Terminals on the indoor unit
1
2
3
Colour of wires
Terminals on the outdoor unit
1
2
3
•
Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor's respectively.
•
Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires for safety reason.
Installation diagram
• The indoor unit may be mounted in any of the three styles shown here.
Front grille
Exposed
Half concealed
Concealed
Air fi lter
Mounting
plate 1
Front panel
Molding
50mm or more
from walls
Floor Installation
Wall Installation
Indoor unit preparation
5 Disengage center hook
• Push in the tab on both sides of front panel to open
front panel.
4 Remove 2 screws
• Unhook the string, lift up the front panel to remove it.
• Slide Shaft to disassemble top vane
• Remove 2 screws and disengage center hook then
1 Push in
tab to unhook
Wall
dismount front grille.
front panel
• For Moldings and Side Piping
• Remove the pillars. (Remove the slit portions on the
bottom frame using nippers.)
Front panel
Refrigerant pipe
70
2 Open and remove front panel
For Moldings
For Side Piping without Moldings
Floor
Bottom frame
Bottom frame
Cut
Cut
Remove the
Remove the
pillars (Cut off)
pillars (Cut off)
Outdoor
Indoor unit installation
15 mm
• For fl oor installations, secure the indoor unit using 6 screws.
• For wall installations, secure the mounting plate 1 using 7 screws and the indoor unit using 4 screws.
Approx. 5 - 7 mm
- Temporarily secure the mounting plate to the wall, make sure that the panel is completely level, and mark the drilling
points on the wall.
• Once refrigerant piping and drain piping connections are complete, fi ll in the gap of the through hole with putty. A gap
Bushing
(Locally purchased)
can lead to condensation on the refrigerant pipe, and drain pipe, and the entry of insects into the pipes.
• Attach the front panel and front grille by following the removal procedure in reverse once all connections are complete.
Putty or caulking compound
Floor Installation
Wall Installation
Mounting plate 1
To access these 2 locations,
To access these 2 locations,
long screw driver is required.
long screw driver is required.
Casing
7 screws 2
(M4 × 25L)
Must be no trap.
Do not touch water.
6 screws 2
4 screws 2
(M4 × 25L)
(M4 × 25L)
Molding
CAUTION
The mounting plate should be installed on a wall
which can support the weight of the indoor unit.
*
For Gas side piping please refer table and diagram below
Outdoor Multi Combination Model
Pipe size
Hall Union
(refer to diagram)
R32 Model
Auxiliary pipe
(male side)
CS-MZ20***,
CU-2Z35***,
CS-Z25***,
CU-2Z41***,
CS-Z35***
CU-2Z50***
Hall Union
CS-Z50***
CU-2Z50***
Auxiliary pipe
(male side)
(CZ-MA1PA)
circumference
Insulating the refrigerant piping
1)
• Attach the pipe after checking for gas leakage,
described above.
1) Cut the insulated portion of the on-site piping,
matching it up with the connecting portion.
2) Secure the slit on the auxiliary pipe side with the butt
joint on the connection pipe using the tape, making
sure there are no gaps.
3) Wrap the slit and the butt joint with the included
insulation sheet 3, making sure there are no gaps .
Do not overtighten, overtightening may cause gas leakage.
Piping size
Torque
Checking for gas leakage
6.35 mm (1/4")
[18 N•m (1.8 kgf•m)]
9.52 mm (3/8")
[42 N•m (4.3 kgf•m)]
• Check for leakage of gas after air purging.
12.7 mm (1/2")
[55 N•m (5.6 kgf•m)]
• See the in the installation manual for the outdoor.
15.88 mm (5/8")
[65 N•m (6.6 kgf•m)]
19.05 mm (3/4")
[100 N•m (10.2 kgf•m)]
CAUTION
Liquid side
Hall Union
1) Insulate the joint of the pipes securely.
Flare Nut
Auxiliary pipe
Incomplete insulation may lead to water leakage.
Connection pipe
(male side)
2) Push the pipe inside so it does not apply undue force on the front grille.
(female side)
WIRE STRIPPING,
Indoor/outdoor
Wire stripping
WARNING
CONNECTING
connection
REQUIREMENT
terminal board
This equipment must be properly earthed.
No loose strand
5 mm or more
when inserted
(gap between wires)
RISK OF FIRE
JOINING OF
WIRES MAY CAUSE
Terminal Board
WARNING
OVERHEATING AND
FIRE.
④
Cable holder
Do not joint wires
⑤
②
Connection cable
Earth Wire
OR
①
OR
longer than
others AC wires
for safety reason
③
Cord
holder
Connection cable
• Remote controller
Signals may not be transmitted and received correctly when the remote controller is operated while in the
holder. Take the remote controller in your hand to operate the unit.
Mount the holder in a location that is not subject to the effects of heat (direct sunlight and stoves, etc.).
70mm or more
50mm or more
Attaching the remote control holder to the wall
from walls
Remote control holder fi xing screws 7
Remote
control 4
Caulk pipe
hole gap
Remote control holder 6
with putty.
Half concealed
installation
• Only item peculiar to this installation method are given here. See
Exposed
installation for additional
instructions.
Top vane
Shaft
3 Slide left to
Wall hole
disassemble
top vane
• Drill a wall hole of the size shown in the illustration on the right.
742-746
(Unit: mm)
6 Remove
Open size
front grille
Opening hole
Floor
Front grille
Installation of supplemental plate for attaching indoor unit
For Side Piping with Moldings
Bottom frame
• The rear of the unit can be fi xed with screws at the points shown in the illustration as below. Be sure
to install the supplemental plate in accordance with the depth of the inner wall.
720
50
Cut
Screw hole
Screw hole
Supplemental plate
(Locally purchased)
135
90
Fixing point
on the back
265
Opening hole
230
250
Remove the
pillars (Cut off)
Supplemental plate
(Locally purchased)
200
CAUTION
• The supplemental plate for installing the main unit must be used, or there will be a gap between the unit and the wall.
Refrigerant piping
See Refrigerant piping under
Exposed
Installation.
Left bottom piping
Right bottom piping
Unit piping position
Hole location
Right/left side piping
Wall
10
• Location for securing the mounting plate.
80
70
(Unit: mm)
CUTTING AND FLARING THE PIPING
1. Please cut using pipe cutter and then remove the burrs.
2. Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused. Turn the piping end down to avoid the metal powder entering the pipe.
3. Please make fl are after inserting the fl are nut onto the copper pipes.
Pipe
Handle
Bar 0 – 0.5 mm
Reamer
Bar
Yoke
Core
Copper pipe
Point down
Clamp handle
Red arrow mark
1. To cut
2. To remove burrs
3. To fl are
Auto switch operation
The below operations will be performed by pressing the "AUTO" switch.
1. AUTO OPERATION MODE
The Auto operation will be activated immediately once the Auto Switch is pressed and release within 5 sec..
2. TEST RUN OPERATION (FOR PUMP DOWN/SERVICING PURPOSE)
The Test Run operation will be activated if the Auto Switch is pressed continuously for more than 5 sec. to below 8 sec..
A "pep" sound will occur at the fi fth sec., in order to identify the starting of Test Run operation.
3. HEATING TRIAL OPERATION
Press the "AUTO" switch continuously for more than 8 sec. to below 11 sec. and release when a "pep pep" sound is occured at eighth sec. (However, a "pep" sound is occurred at fi fth sec..) Then
Gas side
press Remote controller "AC Reset" button once.
Flare Nut
Remote controller signal will activate operation to force heating mode.
Connection pipe
(female side)
4. REMOTE CONTROLLER RECEIVING SOUND ON/OFF
The ON/OFF of Remote controller receiving sound can be change over by the following steps:
a) Press "AUTO" switch continuously for more than 16 sec. to below 21 sec.. A "pep", "pep", "pep", "pep" sound will occur at the sixteenth sec..
Flare Nut
Connection pipe
b) Press the "AC Reset" button once, "pep" sound will occur indicates that Remote controller receiving sound setting mode is activated.
(female side)
c) Press "AUTO" switch again. Everytime "AUTO" switch is pressed (within 60 sec. interval), Remote controller receiving sound status will be reversed between ON and OFF. Long "peep" sound
Pipe size reducer (CZ-MA1PA)
indicates that Remote controller receiving sound is ON. Short "pep" sound indicates that Remote controller receiving sound is OFF.
Heating only operation
1) Use remote controller to set heating only operation. When the unit in standby mode, follow the steps below:
2)
3)
Auxiliary pipe
Auxiliary pipe
Auxiliary pipe
a) Press
continuously for more than 5 seconds to enter special setting mode.
Slit
Slit
b) Press
to choose function 61, and then press
to set "01"
c) Press
SET
to activate "Heating only operation"
Insulation sheet
3
(Function
Tape
no.)
Connection
T 5 secs
pipe
(Options)
Special setting mode
Check for leakage here.
Check the drainage
• Apply soapy water
and check carefully for
leaking gas.
• Open front panel and remove air fi lters.
• Wipe soapy water
(Drainage checking can be carried out without removing the front grille.)
off after the check is
complete.
• Pour a glass of water into the drain tray-styrofoam.
• Ensure that water fl ows out from drain hose of the indoor unit.
Evaluation of the performance
• Operate the unit at cooling/heating operation mode for fi fteen minutes or more.
• Measure the temperature of the intake and discharge air.
• Ensure the difference between the intake temperature and the discharge is more than 8°C during Cooling operation or more than 14°C during
Heating operation.
Conductor
Conductor over
Note:
Conductor not
fully inserted
inserted
fully inserted
• During extremely cold winter, turn on the power supply and standby the unit for at least 15 minutes before test run. Allow suffi cient time to
warm up refrigerant and prevent wrong error code judgement.
ACCEPT
PROHIBITED
PROHIBITED
CHECK ITEMS
Is there any gas leakage at fl are nut connections?
Has the heat insulation been carried out at fl are nut connection?
Is the connection cable being fi xed to terminal board fi rmly?
OR
Is the connection cable being clamped fi rmly?
Is the drainage ok?
(Refer to "Check the drainage" section)
Is the earth wire connection properly done?
Use complete wire without joining.
Use approved socket and plug with earth pin.
Wire connection in this area must follow to
national wiring rules.
2. Selection of Pipe and Heat Insulation Materials
• When using commercial copper pipes and fi ttings, observe the following:
1) Insulation material: Polyethylene foam
Heat transfer rate: 0.041 to 0.052 W/mk (0.035 to 0.045kal/mh°C)
Refrigerant gas pipe's surface temperature reaches 110°C max.
Choose heat insulation materials that will withstand this temperature.
2) Be sure to insulate both the gas and liquid piping and to provide insulation
dimension as below.
Pipe Dimension
Heat Insulation Dimension
Gas side
3/8"(O.D. 9.5mm t0.8mm)
I.D.12-15mm t10mm Min
Liquid side
1/4"(O.D. 6.4mm t0.8mm)
I.D. 8-10mm t10mm Min
3) Use separate heat insulation pipes for gas and liquid refrigerant pipes.
• Required material
Pipe size reducer (CZ-MA1PA) for CS-Z50*** when connect to multi.
Concealed
installation
• Only item peculiar to this installation method are given here. See
Exposed
installation for additional
instructions.
Preparation
• Install the unit according to the instructions below. Failure to do so may cause lead to both
cooling and heating failure and the condensation inside the house.
1) Allow enough space between the main unit and ceiling not to obstruct the fl ow of cool/
warm air.
2) Use remote controller to change the upward air fl ow limit restriction. When the unit in
standby mode, follow the steps below:
a) Press
continuously for more than 5 seconds to enter special setting mode.
b) Press
to choose function 69, and then press
to set "01"
c) Press
SET
to activate "Up/down air swing upper limit restriction"
(Function
Activate or deactivate
no.)
"Air swing upper limit
restriction"
T 5 secs
(Options)
Special setting mode
(Unit: mm)
CAUTION
If there is an obstruction to upward air fl ow, it is recommanded to turn on upward air fl ow limit restriction. Failure to
do so may cause incomplete cooling/heating and formation of condensation inside the house.
70 or more
50 or more
50 or more
Refrigerant piping
Wall
(Unit: mm)
(Unit: mm)
Left bottom piping
Right bottom piping
Hole location
Right/left side piping
50
80
70
35
Improper fl aring
Inclined Surface
Cracked Uneven
damaged
thickness
When properly fl ared, the internal surface of the
fl are will evenly shine and be of even thickness.
Since the fl are part comes into contact with the
connections, carefully check the fl are fi nish.
POWER
TIMER
AUTO SWITCH
Activate or
deactivate "Heating
only operation"
Drain tray-styrofoam
Discharge air
Is the indoor unit properly hooked to the installation plate?
Is the power supply voltage complied with rated value?
Is there any abnormal sound?
Is the cooling/heating operation normal?
Is the thermostat operation normal?
Is the remote control's LCD operation normal?
ENGLISH
ACXF60-60550
PRINTED IN MALAYSIA