13.3 Hysteresis Function (Firmware 1.11d and Newer)

The default settings were already chosen to be suitable for most applications. Changes are
only necessary in exceptions.
To prevent undesired alarms, the new "hysteresis" function was programmed. Hysteresis will
cause the alarm threshold to change after the hysteresis value is exceeded. This requires the
analogue value to enter the permitted area further before the alarm condition stops.
Analogue value
Upper threshold
Measured value
Lower threshold
Alarm
with hysteresis
This hysteresis values are set independently of the alarm value with the following commands:
SET HYSADC <Value> #1513 Refers to function: ADC
SET HYSVOLT <Value> #1513 Refers to function: VOLTAGE
SET HYSTEMP <Value> #1513Refers to function: TEMPERATURE
The value range for the individual commands is:
HYSADC:
HYSTEMP:
HYSVOLT:
The value 0 deactivates this function.
The action TEST for any function displays the current status of all hysteresis values.
RESET resets to the default settings.
Hysteresis
0 ... 99
1 = 0.01 V
0 ... 99
1 = 0.1 °C
0 ... 99
1 = 0.1 V
Alarm without hysteresis
Default: 0.01 V
Default: 0.2 °C
Default: 0.1 V
Hysteresis
Time
Time