AC500-S Sicherheitshandbuch, V1.0.1
8012 BWS unterbro-
chen 2
8013 Warten auf Re-
set 2
4.6.6.12

SF_MutingSeq

Normen
Anforderungen
IEC 61496-1:
A.7 Muting
2004
A.7.1.2 There shall be at least two independent hard-wired muting signal sources to
initiate the function. It shall not be possible to initiate muting when the OSSDs are
already in the OFF-state.
A.7.1.3 The mute function shall only be inititated by the correct sequence and/or
timing of the mute signals. Should conflicting muting signals occur, the ESPE shall
not allow a muted condition to occur.
A.7.1.4 There shall be at least two independent hard-wired muting signal sources to
stop the function. The muting function shall stop when the first of these muting sig-
nals changes state. The deactivation of the muting function shall not rely only on the
clearance of the ESPE.
A.7.1.5 The muting signals should be continuously present during muting. When the
signals are not continuously present, an incorrect sequence and/or the expiration of
a pre-set time limit shall cause either a lock-out condition or a restart interlock.
A.7.4 Indication: A mute status signal or indicator shall be provided (in some appli-
cations, an indication signal of muting is necessary)
Jegliche Vervielfältigung, Verwendung oder Weitergabe an Dritte ist ohne ausdrückliche Genehmigung streng verboten.
© Copyright 2012-2013 ABB. Alle Rechte vorbehalten.
Der Funktionsbaustein hat eine Sicherheitsanforderung erkannt.
Das Schaltelement wurde automatisch getestet.
Ready
= TRUE
S_OSSD_Out
= FALSE
S_TestOut
= TRUE
TestPossible
= FALSE
TestExecuted
= TRUE
Error
= FALSE
Warten auf steigende Flanke von Reset nach Zustand 8012.
Ready
= TRUE
S_OSSD_Out
= FALSE
S_TestOut
= TRUE
TestPossible
= FALSE
TestExecuted
= TRUE
Error
= FALSE
Seite 296/406