GE
Security
ATS626 16 Output Expander
Installation Sheet
EN DA DE ES
FI
FR
1
EN: Installation instructions
Mounting the unit
The ATS626 unit must be fitted to the main control panel using
provided self-locking pillars.
Connections
CON1: Connection to the plug-in connector provided by the ATS
control panel, for example, ATS1000A.
CON3: This connection provides seven 50 mA open collector
outputs (number 1 to 7), and one high current 1 A open collector
output (number 8) with internal pull up. These outputs are
presented on a screw terminal together with +12 VDC and 0 V
(GND) terminals.
Typically, the high current output can be used as an extra siren
IT
NL NO PL PT SV
LK2
CON12
T2
T1
~ ~
+
-
S3 S4 S5
S1 C
AC
BATT
LC-OUTPUTS
HC-OUTPUTS
MI
IP
IP
USB
USB
CON19
CON23
-
-
S2 C
T
C
1
C 2
AUX POWER
SIR TMP
1
output or a similar output device with a temporarily power
requirement.
Note:
Please include the current consumption drawn from the
ATS626 high current output into account when calculating battery
backup capacity for the whole system.
This terminal can also be used to connect ATS1810.
CON5: Eight 50 mA open collector outputs (number 9 to 16).
CON6: Expansion to an ATS18xx clocked output controller
(ATS1811, ATS1820, etc.).
Note:
Clocked relay/open collector cards and the four-way relay
card (ATS1810) cannot be used together on the same device.